Plan Review Notes For Permit 02040518 |
Permit Number |
02040518 |
|
Review Stop |
R |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-07-30 00:00:00 | ************BUILDING PROVISO************ | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) THE STRUCTURE IS LOCATED IN AN "A8" | | FLOOD ZONE AN ELEVATION CERTIFICATE | | WILL BE REQUIRED. | | | | 3) FL BLD CODE 1804.2.2 QUESTIONABLE | | SOILS, WHERE THE BEARING CAPACITY IS | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | SUBMIT SOIL BEARING TESTS PRIOR TO | | POURING THE FOUNDATION. | | | | 4) SUBMIT (2) STORM PANEL INSTALLATION | | SCHEDULE LISTING ALL OF THE OPENINGS | | THAT ARE BEING SHUTTERED. THE ONES THAT | | WERE SUBMITTED ONLY LISTED 7 OF 10 | | OPENINGS. | | | | 5)PROVIDE (2) CURRENT AND COMPLETE | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | EVALUATION REPORTS FOR GLASS BLOCK. ONLY | | PART OF THE REPORT WAS SUBMITTED. |
|