2002-07-30 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUBMIT SOIL BEARING TESTS PRIOR TO
 POURING THE FOUNDATION.
  
 4) SUBMIT (2) STORM PANEL INSTALLATION
 SCHEDULE LISTING ALL OF THE OPENINGS
 THAT ARE BEING SHUTTERED. THE ONES THAT
 WERE SUBMITTED ONLY LISTED 7 OF 10
 OPENINGS.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 EVALUATION REPORTS FOR GLASS BLOCK. ONLY
 PART OF THE REPORT WAS SUBMITTED.