2002-06-27 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE STRUCTURE IS LOCATED IN AN "A8" |
| FLOOD ZONE. AN ELEVATION CERTIFICATE |
| WILL BE REQUIRED. |
| |
| 3) PROVIDE A SOIL BEARING TEST REPORT |
| PER CITY OF WPB AMENDMENTS TO THE 2001 |
| FBC SEC. 1804.2.2. |
| |
| 4) PROVIDE (2) COPIES OF INSTALLATION |
| SCHEDULE FOR STORM PANELS. THESE ARE |
| REQUIRED AT TIME OF PERMIT OR A SEPARATE |
| PERMIT (WITH ADDITIONAL FEES) WILL HAVE |
| TO BE PULLED FOR THE STORM PANELS. |
| |
| 5) PROVIDE ADDITIONAL COPIES OF PRODUCT |
| APPROVALS FOR THE FRONT DOOR AND GLASS |
| BLOCK. TWO COPIES ARE REQUIRED. |
| |
| 6) PROVIDE TESTING INFORMATION FOR GLASS |
| BLOCK WHICH INDICATES BLOCK HAS A ONE |
| HOUR FIRE RATING. |
| |
| 7) PLEASE CHANGE THE CALL SIZE OF THE |
| EGRESS WINDOW (I) IN THE WINDOW SCHEDULE |
| TO 24-5 SH WHICH CORRESPONDS TO THE |
| REVISED DIMENSIONS GIVEN. |
| |
| 8) PLEASE CHANGE NOTE #6 UNDER GENERAL |
| NOTES ON A2 TO REFERENCE THE 2001 |
| FLORIDA PLUMBING CODE. |
| |
| 9) PROVIDE A DETAIL OF THE GABLE END ON |
| THE ZERO LOT LINE. IT IS REQUIRED TO BE |
| A ONE HOUR FIRE RATED ASSEMBLY BASED ON |
| BOTH INTERIOR AND EXTERIOR EXPOSURE TO |
| FIRE. |
| |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |