2002-04-26 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASENOTE CODE ARTS STILL
 FROM 96 NEC.NEEDS TO REF 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT OF AIC
 RATING SHOWN AS 22.00? PLEASE
 CORRLETE TO SHOW 22,000
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROETECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTES. PER210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELEECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372