2002-04-26 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE PLANS ARE STILL
 SHOWING THE 96 NEC. PLEASECORRELATE
 W/ 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR AIC
 RATING SHOWN AS 22.00?? SHOULD SHOW
 22,000.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTES. PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  