2003-09-19 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE E-SHEETS 4.02
 AND 1.00 FOR FEEDERS. 8SETS OF 500MCM
 ON ONE AND 8 SETS OF 600MCM ON OTHER?
  
 2)NOTE: PLEASE ALSO SEE RISER DIAGRAM,
 APPEARS TO HAVE 4000A SW BOARD "2MCR"
 FEEDING A 3000A ALUM, BUS DUCT?
 SHOWN AS K-7.
 PLEASE CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]