Plan Review Notes For Permit 02040459 |
Permit Number |
02040459 |
|
Review Stop |
E |
Sequence Number |
8 |
|
Notes |
Date |
Text |
2003-09-19 00:00:00 | ************** UNSAT *************** | | | | 1)NOTE: PLEASE CORRELATE E-SHEETS 4.02 | | AND 1.00 FOR FEEDERS. 8SETS OF 500MCM | | ON ONE AND 8 SETS OF 600MCM ON OTHER? | | | | 2)NOTE: PLEASE ALSO SEE RISER DIAGRAM, | | APPEARS TO HAVE 4000A SW BOARD "2MCR" | | FEEDING A 3000A ALUM, BUS DUCT? | | SHOWN AS K-7. | | PLEASE CORRELATE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|