Plan Review Notes For Permit 02040459 |
Permit Number |
02040459 |
|
Review Stop |
FIRE |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2004-05-07 00:00:00 | 1) STAIR # 5 SHALL BE EQUIPPED WITH | | A STANDPIPE SYSTEM SINCE IT WILL BE | | USED IN LIEU OF STAIR # 8. | | | | 2) GATES SHALL MEET THE REQUIREMENTS | | FOR LOCKING DEVICES ON PAGE LS-1.09 | | SHALL COMPLY WITH LIFE SAFETY CODE | | REQUIREMENTS. | | | | 3) DOOR SWINGS ARE INCORRECT ON PAGE | | A2.13 FOR STAIRS 1 & 3. | | | | 4) MAGNETIC LOCK NOTED ON DOOR SCHEDULE | | FOR DOOR P4. LOCKS CANNOT INTERFERE | | WITH EXITING. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|