Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop FIRE
Sequence Number 7
Notes
Date Text
2004-05-07 00:00:001) STAIR # 5 SHALL BE EQUIPPED WITH
 A STANDPIPE SYSTEM SINCE IT WILL BE
 USED IN LIEU OF STAIR # 8.
  
 2) GATES SHALL MEET THE REQUIREMENTS
 FOR LOCKING DEVICES ON PAGE LS-1.09
 SHALL COMPLY WITH LIFE SAFETY CODE
 REQUIREMENTS.
  
 3) DOOR SWINGS ARE INCORRECT ON PAGE
 A2.13 FOR STAIRS 1 & 3.
  
 4) MAGNETIC LOCK NOTED ON DOOR SCHEDULE
 FOR DOOR P4. LOCKS CANNOT INTERFERE
 WITH EXITING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910