Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop B
Sequence Number 7
Notes
Date Text
2003-10-01 00:00:00REVISIONS DATED 7/9/03
  
 BRITO-COHAN LETTER DATED 7/11/03 SIGNED
 AND SEALED BY LAWRENCE S. COHAN RE:
 SUBSTITUTION OF FOAM CORE MOLDINGS FOR
 EXTERIOR TRIM.
  
 THE USE OF THIS PRODUCT WAS PREVIOUSLY
 DENIED PRIOR TO ISSUANCE OF THE PERMIT
 WITH CITATIONS OF THE PERTINENT CODE
 SECTIONS FROM THE FBC WHY IT IS
 PROHIBITTED.
  
 FBC 1404.1.1 LIMITS ARCHITECTURAL TRIM
 OF TYPE VI CONSTRUCTION TO BUILDINGS OF
 THREE STORIES OR 40' IN HEIGHT WHEN THE
 BUILDING IS OF TYPE I, II, IV OR V
 CONSTRUCTION.CITY PLAZA IS TYPE I
 CONSTRUCTION AND HIGHER THAN 40'.
  
 FBC F102.2.7 AS AMENDED BY THE CITY
 ALLOWS ARCHITECTURAL TRIM ON BUILDINGS
 IN THE FIRE DISTRICT TO BE ONLY OF
 NON-COMBUSTIBLE MATERIALS OR FIRE
 RETARDANT TREATED WOOD.CLEARLY, THE
 FOAM COATED WITH 0.040" OF POLYURETHANE
 AS DESCRIBED IN THE UNIVERSAL FOAM, INC.
 LETTER IS NEITHER.
  
 THE ARCHITECT'S LETTER ASSERTS THAT A
 FLAME SPREAD OF 25 OR LESS AS DESCRIBED
 IN FBC 803.2 IS EQUIVALENT TO THE CODE
 REQUIREMENTS.
  
 FBC (OR THE FORMER SBC) 803.2 PERTAINS
 TO INTERIOR FINISHES.THIS IS EXTERIOR
 ARCHITECTURAL TRIM.NOTE WORTHY IS 803.
 4 FOAM PLASTICS, THAT PROHIBITS FOAM
 WITH AN EXCEPTION FOR MOLDINGS AND
 SIMILAR, LIMITED TO A MAXIMUM THICKNESS
 OF 1/2" AND A MAXIMUM WIDTH OF 4".
 FURTHER, IT IS CONDITIONED UPON FOAM
 HAVING A DENSITY OF 20 LB/CU FT, NOT
 THE 1.25 LB/CU FT AND TICKNESSES OF 6"
 AND INDETERMINATE WIDTH CALLED FOR IN
 THE UNIVERSAL FOAM, INC. LETTER.
  
 ATTACHED TO THE ARCHITECT'S LETTER FOR
 DATA TO SUBSTANTIATE HIS EQUIVALENCY
 ASSERTION WERE COPIES OF REPORTS FROM
 RADCO LABORATORIES TO THE CARPENTER
 INSULATION COMPANY.
  
 THE PRODUCTS AND ASSEMBLIES IN THE
 REPORTS SUCH AS DRYVIT, PAREX AND STO,
 ARE PERMITTED TO BE USED WHEN INSTALLED
 IN ACCORDANCE WITH THEIR LISTING,
 CURRENT RECOGNIZED EVALULATION REPORT,
 AND MANUFACTURER'S PUBLISHED
 INSTRUCTIONS.
  
 ONE LETTER IS FOR A UL LISTING FOR ROOF
 INSULATION WHICH IS COVERED BY OTHER
 CODE SECTIONS AND NOT A COMPARABLE TO
 THE PROPOSED USE.FURTHER, AS ALL OF
 THE OTHER TEST LETTERS, THE FOAM
 PRODUCT MEETS THE DEFINITION OF A
 COMBUSTIBLE MATERIAL AS DEFINED IN FBC
 202.
  
 IT SHOULD BE NOTED THAT THE
 INTRODUCTION TO THE TEST REPORTS
 CONTAINS THE DISCLAIMER THAT THE TEST
 IS NOT ACCURATE FOR CERTAIN PLASTICS.
  
 THE ARCHITECT'S LETTER SPEAKS TO THE
 ALLOWED USE OF FIRE RETARDANT TREATED
 WOOD.THE DEFINITION OF FRTW SETS OUT
 CRITERIA FOR SPECIFIC TESTING AND TIMES
 TO BE USED WITH ASTM E-84.THE LETTERS
 DO NOT REFLECT THOSE. IN FACT THE SGS
 U.S. LETTER FOR FUTURA COATINGS, IN THE
 OBSERVATION SECTION DESCRIBES "FLAMING
 PIECES FALLING TO THE FLOOR OF THE
 CHAMBER AFTER 2 MINUTES".
  
 THE CHARACTERISTICS OF FOAM AND FRT
 WOOD UNDER FIRE CONDITIONS ARE NOT THE
 SAME NOR IS THIS DEMONSTRATED IN THE
 DATA PROVIDED THUS FAR.
  
 MATERIAL MEETING THE DEFINITION OF
 NON-COMBUSTIBLE IS REQUIRED.
  
 A DEMONSTRATION OF COMPLIANCE WITH FBC
 2603.8 FOAM INSULATION, SPECIAL
 APPROVAL IS A MORE LIKELY "EQUAL AND
 ALTERNATE" THEN THE ARGUMENT PROVIDED.
 IT INCLUDES TESTING IN THE "END USE
 CONFIGURATION".