Plan Review Notes For Permit 02040459 |
Permit Number |
02040459 |
|
Review Stop |
B |
Sequence Number |
62 |
|
Notes |
Date |
Text |
2005-03-15 00:00:00 | ****CORRECTIONS**** | | REVISION #59 | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)FBC1006.1.3.1 PENETRATIONS INTO AND | | OPENINGS THROUGH A STAIRWAY ENCLOSURE | | ASSEMBLY ARE PROHIBITED.REGARDING THE | | LOUVERS IN THE STAIRS, SHOW COMPLIANCE | | WITH ONE OF THE EXCEPTIONS.THIS | | COMMENT MAY ALSO AFFECT THE REVISIONS | | 46, 50 AND 58. | | | | 2.) K-A6.05, LABELED "SCUPPER" ALTHOUGH | | IT APPEARS TO BE AN OVERFLOW DRAIN; | | FBC1503.4.2 OVERFLOW DRAIN SHALL BE | | INSTALLED 2" ABOVE THE LOW POINT OF THE | | ROOF. | | | | 3.)SHEET A11.12, PLEASE NOTE WHERE | | THESE RAILS/GUARDRAILS ARE TO BE | | INSTALLED.NOTE THAT THE NEWEL DETAIL | | HAS BEEN REVISED TO STATE A STEEL TOP | | RAIL BUT SOME OF THE OTHER STAIR DETAILS | | SPECIFY WOOD. | | | | | | | | SOME OF THE REVISIONS 46 - 59 AFFECT | | OTHER TRADES.SUBMIT REVISIONS ON THE | | AFFECTED SHEETS FOR OTHER TRADES IF YOU | | HAVE NOT ALREADY DONE SO. |
|