2005-03-15 00:00:00****CORRECTIONS****
 REVISION #59
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)FBC1006.1.3.1 PENETRATIONS INTO AND
 OPENINGS THROUGH A STAIRWAY ENCLOSURE
 ASSEMBLY ARE PROHIBITED.REGARDING THE
 LOUVERS IN THE STAIRS, SHOW COMPLIANCE
 WITH ONE OF THE EXCEPTIONS.THIS
 COMMENT MAY ALSO AFFECT THE REVISIONS
 46, 50 AND 58.
  
 2.) K-A6.05, LABELED "SCUPPER" ALTHOUGH
 IT APPEARS TO BE AN OVERFLOW DRAIN;
 FBC1503.4.2 OVERFLOW DRAIN SHALL BE
 INSTALLED 2" ABOVE THE LOW POINT OF THE
 ROOF.
  
 3.)SHEET A11.12, PLEASE NOTE WHERE
 THESE RAILS/GUARDRAILS ARE TO BE
 INSTALLED.NOTE THAT THE NEWEL DETAIL
 HAS BEEN REVISED TO STATE A STEEL TOP
 RAIL BUT SOME OF THE OTHER STAIR DETAILS
 SPECIFY WOOD.
  
  
  
 SOME OF THE REVISIONS 46 - 59 AFFECT
 OTHER TRADES.SUBMIT REVISIONS ON THE
 AFFECTED SHEETS FOR OTHER TRADES IF YOU
 HAVE NOT ALREADY DONE SO.