6 |
|
Notes |
Date |
Text |
2004-08-20 00:00:00 | DENIED: | | 1.PLAN SHEET M2.02 INDICATES REV #3 ON | | THE PLAN BUT DOES NOT INDICATE THE DATE | | OF THE REVISION ON THE REVISION SCHEDULE | | OR THE DRAWING NARRATIVE. | | | | 2.PLAN SHEET M2.04 UNIT 11L DOES NOT | | INDICATE RETURN AIR FROM BEDROOM #2. | | | | 3.PLAN SHEET 2.35 & M5.05, PLANS | | INDICATE 2 COOLING TOWERS DELETED & | | MANUFACTURER CHANGED.PROVIDE SUBMITTAL | | FOR REVISED COOLING TOWER. | | | | 4.PLEASE NOTE THIS CHANGE ALSO AFFECTS | | THE ENERGY CALCULATIONS PLEASE REVISE | | ENERGY CALCS. | | | | 5.TONNAGE & GPM CHANGED ON THE COOLING | | TOWER, PLEASE PROVIDE CALCULATIONS | | DEMONSTRATING THAT THEY WILL MEET THE | | DEMAND. | | | | 5.PLEASE NOTE MECHANICAL JOINTS | | (VICTALIC FITTINGS, COUPLINGS, ETC) ARE | | TO BE READYLY ACCESSIBLE. 2001 FBC(M) | | 1209.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|