2004-08-20 00:00:00DENIED:
 1.PLAN SHEET M2.02 INDICATES REV #3 ON
 THE PLAN BUT DOES NOT INDICATE THE DATE
 OF THE REVISION ON THE REVISION SCHEDULE
 OR THE DRAWING NARRATIVE.
  
 2.PLAN SHEET M2.04 UNIT 11L DOES NOT
 INDICATE RETURN AIR FROM BEDROOM #2.
  
 3.PLAN SHEET 2.35 & M5.05, PLANS
 INDICATE 2 COOLING TOWERS DELETED &
 MANUFACTURER CHANGED.PROVIDE SUBMITTAL
 FOR REVISED COOLING TOWER.
  
 4.PLEASE NOTE THIS CHANGE ALSO AFFECTS
 THE ENERGY CALCULATIONS PLEASE REVISE
 ENERGY CALCS.
  
 5.TONNAGE & GPM CHANGED ON THE COOLING
 TOWER, PLEASE PROVIDE CALCULATIONS
 DEMONSTRATING THAT THEY WILL MEET THE
 DEMAND.
  
 5.PLEASE NOTE MECHANICAL JOINTS
 (VICTALIC FITTINGS, COUPLINGS, ETC) ARE
 TO BE READYLY ACCESSIBLE. 2001 FBC(M)
 1209.3.
  