2004-07-30 00:00:00****PROVISO****
 REVISION ADDRESSING COMMENTS 6/1/02
 THROUGH REVISION #44
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SHEET A1.04 STILL SHOWS SLOPES OF
 1:35 AND 1:38 FOR THE ACCESSIBLE PARKING
 SPACE.THIS IS NOT COMPLIANT WITH
 FBC11-4.6.3; "PARKING SPACES AND ACCESS
 AISLES SHALL BE LEVEL WITH SURFACE
 SLOPES NOT EXCEEDING 1:50 (2%) IN ALL
 DIRECTIONS."SEE REVIEW SET; ABOVE
 REFERENCED SLOPES HAVE BEEN HIGHLIGHTED.
 REVISE SHEET A1.04
  
 2.)DOORS IN THE STAIRWAY ENCLOSURES
 TO COMPLY WITH FBC705.1.3.4.
  
 3.)REVISE SHEET 1.06 (NO WHITEOUT)
  
 4.)PROVIDE A FIREBLOCKING
 DETAIL FOR THE DROPPED CEILINGS SHOWN
 ON A5.12 FBC705.3.1.1.
  
 5.)PROVIDE CALCULATIONS FOR STAIR #5
 (FBC412.11(5)).