Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop P
Sequence Number 5
Notes
Date Text
2003-08-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) RISERS 43/55/44/12 6TH THROUGH 10TH
 FLOOR. WHEN A HORIZONTAL STACK OFFSET IS
 LOCATED MORE THAN FOUR BRANCH INTERVALS
 BELOW THE TOP OF THE STACK, A HORIZONTAL
 BRANCH SHALL NOT CONNECT WITHIN THE
 HORIZONTAL STACK OFFSET OR WITHIN 2 FEET
 ABOVE OR BELOW SUCH OFFSET. SEC 711.2
 SHT P3.16 (WASH MACHINE)
 2) RISER #1 SEE COMMENT #1 (BATHROOM AND
 SINK) SHT P3.14
 3) RISER #2 6TH FLOOR W/M DRAINS THROUGH
 BATHROOM GROUP. SEC 909.1 SHTP3.14 ALSO
 RISERS 53/50/51
 4) RISERS 34/58/25 KITCHEN SINK CONNECT-
 ED IN HORIZONTAL OFFSET. (SEE COMMENT #
 1)
 5) RISER #13 SHT P3.16 KITCHEN SINK
 CONNECTED IN OFFSET. (SEE COMMENT #1)
 6) RISER #52 SAME AS RISER #1.
 7) SECTION 917.3.2 RELIEF VENT REQUIRED
 TO AIR ADMITTANCE VALVES. ALL 8 A.A.V'S
 WILL WILL REQUIRE A RELIEF VENT.
 8) PLANS SHALL BE PICKED UP AND RESUB-
 MITTED. PER CITY CODE A 10% RESUB FEE
 WILL BE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved