Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop P
Sequence Number 4
Notes
Date Text
2003-08-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEW: ALL UNITS - WET
 VENTS IN BATHROOMS, ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 KICHEN SINKS, AND WASH MACHINES SHALL
 NOT DRAIN THROUGH BATHROOMS. SEC 909.1
 THE FOLLOWING LIST STILL NEEDS TO BE
 CORRECTED.
 SHT P2.11 UNITS 35 & 36 - RISERS 3 & 48
 SHT P2.12 UNIT 24RISERS 11/43/55/44/12
 SHT P2.14 UNIT 1 (RISER NOT SHOWN)
 SHT P2.19 UNIT Q - RISER 1
 SHT P2.19 UNIT B3 - RISERS 2/53
 SHT P2.19 UNIT B5 - RISERS 50/51
 SHT P2.20 UNIT B2 - RISER 13
 SHT P2.22 UNIT B6 - RISERS 34/58/25
 SHT P2.26 UNIT J2 - RISERS 31/32
 SHT P2.27 UNIT BD - RISER 5
 SHT P2.35 UNIT G1 - RISERS 1 & 2
 SHT P2.35 UNIT B7 - RISER 46
 SHT P2.35 UNITO - RISER 4
 SHT P2.35 UNITG - RISERS 51/52
 SHT P2.36 UNITL - RISER 45
 SHT P2.36 UNITN - RISER 43
 SHT P2.36 UNITM - RISER 12
 SHT P2.38 UNITC - RISER 28
 SHT P2.38 UNIT 01 - RISER 23
 2) SHT P3.13 FLOOR DRAIN IN TRASH TER-
 MINATION ROOM NOT VENTED. ALSO NEW LINE
 TO FLOOR DRAIN FOR FIRE SYSTEM HUB DRAIN
 NOT VENTED.
 3) SHT P.13 FLOOR DRAIN IN BREEZEWAY
 STILL SHOWN ON THE SANITARY RISER DIA-
 GRAM. THIS WAS CHANGED TO STORM.
 4) FROM THE PREVIOUS REVIEW: (#10 FROM
 LAST REVIEW) SHT P.13 SHOWS PIPING THAT
 IS NOT SHOWN ON THE GROUND LEVEL LOBBY
 AREAS, (PLAN VIEW). SUBMIT A SHEET THAT
 SHOWS THE PLAN VIEW AREA BETWEEN THE
 NORTH AND SOUTH SECTIONS THAT REFLECTS
 THE RISER DIAGRAM FOR THIS AREA.
 5) FROM PREVIOUS REVIEW: SHT P3.10 PIPE
 SIZE NOT SHOWN FOR RWL IN SOME AREAS.
 SOME PIPE SIZES STILL ARE NOT INDICATED
 AS REQUESTED. SEE RED LINE AREAS INDICA-
 TED ON PLANS.
 6) FROM PREVIOUS REVIEW: SEPARATE BACK-
 FLOWS REQUIRED FOR POOL AND IRRIGATION.
 7) FROM PREVIOUS REVIEW: SHT P2.43 THE
 WASTE FROM THE BACKWASH SHAL DRAIN TO
 SANITARY. DETAIL SHOWS BACKWASH DRAINING
 TO STORM. OVERFLOW ONLY TO STORM.
 8) FROM PREVIOUS REVIEW: (#30) RESPONSE
 INDICATES THAT STACK 30 IS NOW A CONVEN-
 TIONAL WASTE STACK AND VENT STACK, BUT
 THE STACK HAS BEEN DELETED. PLEASE
 CLAIRFY.
 9) SHT P3.15 RISER #8 DOES NOT REFLECT
 THE FLOOR PLAN. SHT P2.36 UNIT A SHOWS
 IN CLOUDED AREA 3" WASTE FROM ABOVE.
 RISER #8 SHOWS 3 LAVS AND NO 3" WASTE
 FROM ABOVE. PLEASE CLAIRFY. (IF 3" WASTE
 FROM ABOVE, IT SHALL TIE IN DOWNSTREAM
 OF THE BATHROOM GROUP. 909.1)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]