2003-07-29 00:00:00PROVISO:
  
 AS PER OUR MEETING 7-25-03, GENERATOR
 EXHAUST SHALL TERMINATE A MINIMUM OF
 10 FT FROM ANY WINDOW, DOOR, OR FRESH
 AIR INTAKE.AFTER FURTHER RESEARCH
 NFPA 110 SECTION 7.10.2, EXHAUST
 INSTALLATION SHALL TERMINATE IN SUCH A
 MANNER THAT TOXIC FUMES CANNOT REENTER
 A BUILDING OR STRUCTURE, PARTICULARY
 THROUGH WINDOWS, AIR VENTILATION INLETS
 OR ENGINE AIR-INTAKE SYSTEM.
  