Plan Review Notes For Permit 02040459 |
Permit Number |
02040459 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2003-07-29 00:00:00 | PROVISO: | | | | AS PER OUR MEETING 7-25-03, GENERATOR | | EXHAUST SHALL TERMINATE A MINIMUM OF | | 10 FT FROM ANY WINDOW, DOOR, OR FRESH | | AIR INTAKE.AFTER FURTHER RESEARCH | | NFPA 110 SECTION 7.10.2, EXHAUST | | INSTALLATION SHALL TERMINATE IN SUCH A | | MANNER THAT TOXIC FUMES CANNOT REENTER | | A BUILDING OR STRUCTURE, PARTICULARY | | THROUGH WINDOWS, AIR VENTILATION INLETS | | OR ENGINE AIR-INTAKE SYSTEM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|