2003-05-20 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE SHEETS 5.12 AND 5.13
 OF ALL SETS. PLANS NOT SIGNED, DATED AND
 SEALED BY ENGINEER OF RECORD. PER
 FS 471.
  
 2)NOTE: PLEASE SEE 5.14, PLANS WERE
 REVISED W/ NOTE THAT INDICATES GFI
 PROTECTION FOR MSB, BUT NOT FOR 1MCR,
 2MCRS, 3MCRS(TYP). 230-95,240-13
  
 3)NOTE: PLEASE SEE PANELS THAT ARE
 REVERSED ON 2.12,2.13, AND 2.33.
  
 PLANS ARE COMING BACK FOR COMMENTS FROM
 OTHER REVIEWS. PLEASE ADDRESS THE ABOVE
 AT THIS TIME AND IF 2002 NEC WHICH IS
 REFERENECED ON MANY SHEETS CAN BE CHANG-
 -ED AT THIS TIME. IF NOT, THEN MUST BE
 REDLINED. I HAVE REDLINED ONE SET.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLANS HAVE HAD ALMOST ALL COMMENTS
 ADDRESSED AND ARE IN GOOD SHAPE.
  