Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop B
Sequence Number 30
Notes
Date Text
2004-06-01 00:00:00****CORRECTIONS****
 ARCHITECTURAL REVISION, VARIOUS
 SHEETS, DATED 4/12/04
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SHEET A1.04 SHOWS TWO SLOPES
 GREATER THAN 1:50, NOT COMPLIANT WITH
 FBC11-4.6.3. (SEE REVIEW SET)
  
 2.)SHEET A2.02 IS NOT SIGNED AND
 SEALED ON REVIEW SET.
  
 3.)SHEET A1.06, AT 17'5" ELEVATION,
 STAIR 3, WHAT IS THE PURPOSE OF THE
 DOOR IN THE MIDDLE OF THE STAIR LANDING?
  
 4.)THE REVISIONS AFFECT MEPS.SUBMIT
 THE REVISIONS AS NECESSARY.
  
 5.)SHEETS 5.08 AND 5.09, WHERE IS
 THE DETAIL FOR THE METAL STUD WALLS?
 THE RECENT STRUCTURAL REVISION
 SUBMITTED SHOWS THESE WALLS AS A TYPE
 W3, CONCRETE WALL.TRANSMITTAL LETTER
 INDICATES THE WALLS AS "SHOWN WITHOUT
 CONCRETE - TO BE METAL STUD
 CONSTRUCTION."PLEASE CLARIFY.
  
 6.) A3.09 REFERS TO FOAM COLUMN AND
 PANEL.ARCHITECTURAL TRIM ON BUILDINGS
 LOCATED IN THE FIRE DISTRICT SHALL BE
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED
 WOOD, F102.2.7 CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC, FBC1404.
  
 7.)PROVIDE CALCULATIONS FOR STAIR
 #5, THE NEW EGRESS STAIR, TO SHOW
 COMPLIANCE WITH FBC412.11(5).
  
 8.)DOORS IN THE STAIRWAY ENCLOSURES
 ARE TO COMPLY WITH FBC705.1.3.4.
  
 9.)PROVIDE A DETAIL FOR TYPE I
 REFERRED TO ON SHEET 5.12 (2 HR SHAFT).
  
 10.) SHEET 6.04, PROVIDE A CONSTRUCTION
 DETAIL, INCLUDING METHOD OF ATTACHMENT
 TO THE BUILDING, FASTENING CONNECTION
 DETAILS.
  
 11.) TRASH CHUTES SHALL COMPLY WITH
 NFPA82 3-2.4.3.1, THE SIZE OF THE
 SERVICE OPENING ROOM OR COMPARTMENT
 SHALL NOT BE LESS THAN THAT REQUIRED TO
 MAINTAIN A MINIMUM OF 6" CLEARANCE
 BETWEEN THE OPEN LOADING DOOR AND THE
 CLOSED SERVICE OPENING ROOM DOOR.