2003-06-03 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| |
| A) FROM PREVIOUS REVIEW: - NOT ADDRESSED |
| 1) SHT P2.01 VENT REQUIRED IN TRASH ROOM |
| 2) ALL UNITS - WET VENTS IN BATHROOMS, |
| ONLY THE FIXTURES WITHIN THE BATHROOM |
| GROUPS SHALL CONNECT TO THE WET-VENTED |
| HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| FIXTURES SHALL DISCHARGE DOWNSTREAM OF |
| THE WET VENT. (KITCHEN SINKS AND WASH- |
| MACHINES SHALL NOT DRAIN THROUGH BATH- |
| ROOMS.) SEC 909.1 - THESE CONDITIONS |
| SHALL BE CORRECTED ON THE SANITARY RISER |
| DIAGRAMS AND ALL FLAT LAYOUTS. |
| 3) SHT P2.31 HORIZONTAL RWL NOT SIZED |
| PROPERLY. SHOWS 4" @ 2900 SQ FT & 2800 |
| SQ FT. (ORIGINAL #16) RESPONSE NOTED, |
| BUT NO CHANGE NOTED. |
| 4) SHT P2.39 PLEASE SUBMIT CALCULATIONS |
| FOR PRIMARY AND SECONDARY ROOF DRAINS. |
| SHOW ALL AREAS OF ROOFS THAT DRAIN TO |
| ROOF FROM ABOVE. (NOT SHOWN IN CALCULAT- |
| IONS AS REQUESTED IN COMMENT #19 IN 1ST |
| REVIEW.) |
| 5) SHTS P2.40 & P2.41 PIPE SIZING FOR |
| VENT HEADER SHALL BE SIZED PER TABLE |
| 916.1. SECTION FROM VENT #10 BACK TO |
| WHERE VENT #44 TIES IN PAST #12 SHALL |
| BE 5". 4" PIPE SHOWN. (COMMENT TO RES- |
| PONSE FROM COMMENT #21 1ST REVIEW). |
| 6) SHT P2.44 SHOW PIPE SIZE FOR RWL. |
| SHOWS 6" @ 4000 SQ FT, BUT ITS ACTUALLY |
| IT'S 5000 SQ FT AND SHOULD BE 8" PIPE. |
| RESPONSE NOTED BUT NO CHANGE NOTED. |
| (COMMENT #22 FROM 1ST REVIEW.) |
| 7) SHT P2.05 VENT REQUIRED FOR FLOOR |
| DRAIN IN BREEZEWAY DRIVE. (RESPONSE |
| NOTED, BUT VENT REQUIRED) #24 1ST REV. |
| 8) SHT P2.05 VENTS REQUIRED FOR FLOOR |
| DRAINS IN TRASH ROOM AND TRASH TERMIN- |
| ATION ROOM. (RESPONSE NOTED, BUT VENTS |
| REQUIRED.) #25 1ST REV. |
| 9) SHTS P2.01 THRU P2.05 CLEANOUTS REQ- |
| UIRED BY SECTIONS708.3, 708.3.1, 708.3.3 |
| & 708.3.4 SHALL BE SHOWN ON SHTS P2.01 |
| THRU P2.05, HORIZONTAL PLUMBING LAYOUT, |
| AND NO SHT P3.13 HORIZONTAL SANT. RISER |
| DIAGRAM. (NEW COMMENT) |
| 10) SHT P3.13 SHOW PIPING THAT IS NOT |
| SHOWN ON GROUND LEVEL LOBBY AREAS. |
| PLEASE SUBMIT A SHEET THAT SHOWS THE |
| AREA BETWEEN THE NORTH SIDE AND THE |
| SOUTH SIDE TO SHOW HOW PIPING TIES IN |
| FOR AREA NOT SHOWN. SEC 104.2.1 |
| 11) SHT P2.49 UNABLE TO VERIFY RESPONSE, |
| SHEET IS COMPLETLY CHANGED AND ONE COPY |
| OF ALL SHEETS THAT HAVE BEEN REMOVED AND |
| OR REVISED FOR COMPARISON. #26 1ST REV. |
| 12) SHT P2.49 INFORMATION FOR FOUNTAIN |
| SHALL BE SUBMITTED AT TIME FOR PERMIT |
| APPLICATION. SEPARATE PERMIT REQUIRED. |
| #27 1ST REV. |
| 13) SHTS P3.02,P3.03,P3.04,P3.05,P3.06, |
| P3.07, & P3.08 WATER HAMMER ARRESTORS |
| SHALL BE INSTALLED AT EVERY WASH MACHINE |
| ICE MAKER & DISHWASHER. SOME W/M'S SHOW |
| THEM AND SOME KITCHEN SINKS SHOW THEM, |
| BUT NOT ALL HAVE THEM SHOWN WERE REQUIR- |
| ED BY SECTION 604.9. #28 1ST REV. |
| 14) SHT P3.09 RWL SHOWS 4" @ 1900 SQ FT |
| ON VERTICAL. BUT RISER ALSO RUNS HORIZ- |
| ONTAL, (OFFSET). 5" RISER REQUIRED. RE- |
| SPONSE NOTED BUT NOT ADDRESSED. #30 1ST |
| REVIEW. TABLE 1106.3 |
| 15) SHT P3.10 RWL BY DECK, NO PIPE SIZE |
| SHOWN. RESPONSE NOTED BUT SIZE NOT SHOWN |
| #31 1ST REV. |
| 16) SHT P3.10 RWL RISER ALSO RUNS HORIZ- |
| ONTAL, 8" RISER REQUIRED. RESPONSE NOTED |
| BUT SIZE NOT CORRECTED. #32 1ST REV. |
| 17)SHT P3.10 RWL RISER SHOWS 5" @3000 SQ |
| FT PICKING UP 2 ROOF DRAINS. HORIZONTAL |
| RUNS, 6" REQUIRED. RESPONSE NOTED BUT |
| CORRECT SIZE NOT SHOWN. #33 1ST REV. |
| 18) SHT P3.10 PIPE SIZE NOT SHOWN FOR |
| RWL IN SOME AREAS. RESPONSE NOTED BUT |
| SOME PIPE SIZES STILL NOT SHOWN. PLEASE |
| RECHECK ALL PIPING FOR RWL RISER DIAGRAM |
| AND SIZE ALL PIPE AND RECHECK FOR CORR- |
| ECT SIZE PER TABLE 1106.3#34 1ST REV. |
| 19) SHT P3.10 RWL RISER SHOWS 6" @ 6900 |
| SQ FT, REQUIRES 8" AT HORIZONTAL RUN. |
| RESPONSE NOTED, BUT SIZE NOT CHANGED. |
| #36 1ST REVIEW. |
| 20) SHT P3.10 RWL RISER SHOWS 5" @ 5700 |
| SQ FT HORIZONTAL RUNS REQUIRE 8" PIPE. |
| RESPONSE NOTED BUT PIPE SIZE NOT CHANGED |
| #37 1ST REV. |
| 21) SHT P3.13 FLOOR DRAIN NOT VENTED. |
| RESPONSE NOTED, VENTS STILL REQUIRED. |
| TABLE 906.1 |
| 22) SHT A5.11 FOUNTAIN EQUIPMENT AREA |
| MORE INFO REQD. RESPONSE REFERS TO SHT |
| A5.11 WHICH REFERS TO L.S. PLANS. NO |
| LS PLANS FOUND. PLEASE CLAIRFY. #44 1ST |
| REVIEW. |
| 23) SHTS A8.01 THRU A8.14 RESPONSE NOTED |
| FOR WATER COOLERS AT LIVE/WORK LOFTS. |
| MANUF. INFO. REQUIRED FOR WATER COOLERS |
| AT TIME OF FINAL. 410.1 |
| 24) SHTS A8.12/A8.13 TERRACE DRAINS. RE- |
| SPONSE NOTED, BUT SHTS P2.32 & P2.33 DO |
| NOT REFLECT SHTS A8.12 & A8.13. 11TH FL |
| AND 4TH FLOOR. PLEASE CLAIRFY. #49 1ST |
| REVIEW. |
| 25) PLEASE SUBMIT TYPE OF MATERIAL USED |
| FOR PAN DRAIN, RELIEF VALVE PIPING. RE- |
| SPONSE NOTED BUT MATERIAL NOT SHOWN. #55 |
| 1ST REVIEW. |
| 26) BACKFLOW REQUIRED FOR SWIMMING POOL, |
| IRRIGATION, AND MAKE UP WATER FOR THE |
| COOLING TOWERS. RESPONSE NOTED, BUT EACH |
| SYSTEM SHALL BE PROVIDED WITH BACKFLOW |
| PROTECTION. PLEAS INDICATE HOW EACH SYS- |
| TEM HAS BACKFLOW PROTECTION. #58 1ST REV |
| 28) RESPONSE NOTED FOR POOL PUMP AND |
| EQUIPMENT ROOM, SEPARATE PERMIT REQUIRED |
| FOR POOL. WASTE SHALL DRAIN TO SANITARY |
| AND OVERFLOW SHALL DRAIN TO STORM. PRO- |
| VIDE DETAIL FOR EACH. #59 1ST REVIEW. |
| 29) SHTS P2.02 & P2.05 FIRE SPRINKLER |
| SYSTEM DRAIN SHALL DRAIN TO SANITARY NOT |
| STORM AS INDICATED. PLEASE REVISE |
| 30) SHT P3.14 WASTE STACK #30 SECTION |
| 910.2 THE STACK SHALL BE VERTICAL AND |
| BOTH HORIZONTAL & VERTICAL OFFSETS SHALL |
| BE PROHIBITED. |
| 31) SHT P2.44 TABLE 906.1 MAXIMUM DIS- |
| TANCE OF FIXTURE TRAP FROM VENT FOR A |
| 3" TRAP IS 10'. FLOOR DRAINS FOR THE |
| SAUNA AND THE STEAM ROOM SEEM TO EXCEED |
| THIS AMOUNT. |
| ********WHEN RESUBMITTING PLANS******** |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |