Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop M
Sequence Number 3
Notes
Date Text
2003-05-19 00:00:00DENIED:
  
 1.COMMENT #2, M.2.01 - FIRE DAMPER NOT
 INDICATED AT FLOOR (ONE ADDED AT WALL).
  
 2.COMMENT #12 FROM REVIEW DATED
 5-13-02, OUTSIDE AIR CALCS REQUIRED.
 PLEASE INDICATE OUTSIDE AIR CALCS FOR
 RESIDENTIAL & COMMON AREAS PER 2001 FBC
 (M) TABLE 403.3.
  
 3.PROVIDE VENTILATION REQUIREMENTS
 FOR GENERATOR ROOMS AND ALL MECHANICAL
 & PUMP ROOMS.INDICATE TERMINATION OF
 THE MUFFER EXHAUST AS WELL AS A DETAIL
 ON THE VENTILATION (INTAKE LOUVER &
 EXHUAST).
  
 4.ADDITIONAL PERMIT REQUIRED FOR FUEL
 OIL.PLEASE PROVIDE PLAN INDICATING
 PIPE SIZING & LAYOUT.PLEASE NOTE
 PRESSURE TEST REQUIRED ON PIPING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.