Plan Review Notes For Permit 02040459 |
Permit Number |
02040459 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-05-19 00:00:00 | DENIED: | | | | 1.COMMENT #2, M.2.01 - FIRE DAMPER NOT | | INDICATED AT FLOOR (ONE ADDED AT WALL). | | | | 2.COMMENT #12 FROM REVIEW DATED | | 5-13-02, OUTSIDE AIR CALCS REQUIRED. | | PLEASE INDICATE OUTSIDE AIR CALCS FOR | | RESIDENTIAL & COMMON AREAS PER 2001 FBC | | (M) TABLE 403.3. | | | | 3.PROVIDE VENTILATION REQUIREMENTS | | FOR GENERATOR ROOMS AND ALL MECHANICAL | | & PUMP ROOMS.INDICATE TERMINATION OF | | THE MUFFER EXHAUST AS WELL AS A DETAIL | | ON THE VENTILATION (INTAKE LOUVER & | | EXHUAST). | | | | 4.ADDITIONAL PERMIT REQUIRED FOR FUEL | | OIL.PLEASE PROVIDE PLAN INDICATING | | PIPE SIZING & LAYOUT.PLEASE NOTE | | PRESSURE TEST REQUIRED ON PIPING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|