2003-06-02 00:00:00 | 1) PLEASE PROVIDE MORE INFORMATION WITH |
| REGARDS TO GLASS IN LOBBY DOORS THAT ARE |
| PROTECTED WITH A SPRINKLER HEAD ON EACH |
| SIDE OF GLASS. WATER CURTAINS ARE NOT |
| DESIGNED TO PROTECT DOORS. PLEASE |
| PROVIDE RECOGNIZED TEST DATA. |
| |
| 2) ALL EXIT STAIRS THAT TERMINATE INTO |
| EXIT PASSAGEWAYS SHALL HAVE THE SAME |
| FIRE PROTECTION RATING AS THE STAIRS. |
| |
| 3) THE PLAN PROPOSED A 1000 GPM FIRE |
| PUMP. AGAIN THIS INFORMATION DOES NOT |
| APPEARS TO BE CORRECT. ALL REQUIRED |
| STAIRS FOR THE BUILDING SHALL HAVE |
| STANDPIPE CONNECTIONS. IF EIGHT STAIRS |
| ARE REQUIRED, THEN IN REALITY A 1000 GPM |
| FIRE PUMP IS NOT LARGE ENOUGH. PLEASE |
| ADVISE. |
| |
| 4) PLEASE EXPLAIN GATES AND CARD READERS |
| AND HOW DO THEY AFFECT EXITING. |
| |
| 5) PLEASE EXPLAIN OPEN UNPROTECTED |
| STAIRS. |
| |
| 6) PLEASE PROVIDE FIRE RATING FOR STAIR |
| # 10. |
| |
| 7) STAIR # 5 APPEARS TO BE OPEN PLEASE |
| EXPLAIN RATIONALE. |
| |
| 8) HOW DO YOU DIRECT PEOPLE VIA STAIRS |
| ACROSS AREAS OF PARKING TO REACH |
| ENCLOSED EXIT STAIRS. |
| |
| 9) MORE DETAILS NEEDED ON ROUND FORM |
| COLUMNS SHOWN ON A3.01. |
| |
| 10) KNOX-BOXES ARE TO BE INSTALLED ON |
| THE EXTERIOR OF THE BUILDING. |
| |
| 11) EXIT ACCESS ON MAIN ROOF LEVEL PLAN |
| NOTED THRU DEDICATED AREA FOR LEASABLE |
| SPACE. |
| |
| 12) EXPANDED POLYSTYRENE NOTED IN |
| BUILDING SECTIONS 3 & 3A. |
| |
| 13) PLEASE PROVIDE INFO ON 1" INSULATION |
| AROUND TRASH CHUTE. |
| |
| 14) PLEASE EXPLAIN WHY EXITING ON LS 102 |
| GOES THRU BICYCLE STORAGE AND WHAT CODE |
| REFERENCE ALLOWS THIS. |
| |
| 15) SMOKE DETECTORS ARE REQUIRED IN ALL |
| MECHANICAL, ELECTRICAL, TRANSFORMER AND |
| TELEPHONE EQUIPMENT ROOMS PER 412.2 . |
| |
| NATE MCCRAY, CAPTAIN |
| 659-8096, EXT 8497 |
| 805-6722 OR 835-2910 |