Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop E
Sequence Number 27
Notes
Date Text
2006-03-29 00:00:00PG. E3.01GENERATOR DETAILS BLANK?
  
 PG. E3.02MAIN ELECTRICAL ROOM NOT TO
 PLANS
  
 6TH FLOOR TRANSFORMERS NOT
  
 CORRECT.
  
 PG. E2.24KITCHEN AND FITNESS ROOM
 REVISED. NOT TO PLAN
  
 PG. E2.52NO GFI PROTECTION FOR LIGHTS.
 AT THE FOUNTAIN.
  
 PG. E5.3PLAN CALLS FOR METAL ROOF?
  
 PG. E5.12LABEL SYSTEM NOT USED FOR
 PANELS
  
 PG. E5.10PVC TO BE USED ON PLAN MC
 INSTALLED.
  
 #2/0 USED ON RUNS OVER 200'
  
 LONG.
  
 PG. E4.01METAL LABELS NOT USED.
  
 PG. E6.01FUSES NOT IN THE FIXTURES.
  
 PG. E2.03NO SHUNT TRIP INSTALLED OR
 GENERATOR CONTROLER.
  
 PG. E2.51NOTE 4 WIRE SIZES?
  
 PAGE WITH ALL THE NOTES THAT NEED TO BE
 ADDRESSED WAS NOT SUBMITTED WITH PLANS.
  
 MASTER LABEL FOR THE LIGHTNING
 PROTECTION SYSTEM NOT INSTALLED.
  
 WEATHERPROOF HORN/STROBE ATTACHED TO A
 NON-WEATHERPROOF BOX STICKING OUT 2".
  
  
  