Plan Review Notes For Permit 02040459 |
Permit Number |
02040459 |
|
Review Stop |
E |
Sequence Number |
27 |
|
Notes |
Date |
Text |
2006-03-29 00:00:00 | PG. E3.01GENERATOR DETAILS BLANK? | | | | PG. E3.02MAIN ELECTRICAL ROOM NOT TO | | PLANS | | | | 6TH FLOOR TRANSFORMERS NOT | | | | CORRECT. | | | | PG. E2.24KITCHEN AND FITNESS ROOM | | REVISED. NOT TO PLAN | | | | PG. E2.52NO GFI PROTECTION FOR LIGHTS. | | AT THE FOUNTAIN. | | | | PG. E5.3PLAN CALLS FOR METAL ROOF? | | | | PG. E5.12LABEL SYSTEM NOT USED FOR | | PANELS | | | | PG. E5.10PVC TO BE USED ON PLAN MC | | INSTALLED. | | | | #2/0 USED ON RUNS OVER 200' | | | | LONG. | | | | PG. E4.01METAL LABELS NOT USED. | | | | PG. E6.01FUSES NOT IN THE FIXTURES. | | | | PG. E2.03NO SHUNT TRIP INSTALLED OR | | GENERATOR CONTROLER. | | | | PG. E2.51NOTE 4 WIRE SIZES? | | | | PAGE WITH ALL THE NOTES THAT NEED TO BE | | ADDRESSED WAS NOT SUBMITTED WITH PLANS. | | | | MASTER LABEL FOR THE LIGHTNING | | PROTECTION SYSTEM NOT INSTALLED. | | | | WEATHERPROOF HORN/STROBE ATTACHED TO A | | NON-WEATHERPROOF BOX STICKING OUT 2". | | | | | | |
|