Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop E
Sequence Number 23
Notes
Date Text
2005-09-19 00:00:00REVISION 66
  
 PAGE 2.02SUBMIT DETAIL ON LOW VOLTAGE
 TRANSFORMER FOR LOW VOLTAGE
 ROPE LIGHTINGSIZE OF TRANS
 OVERCURRENT PROTECTION.
 SHOW LOCATION OF TRANS, DISC.
  
 PAGE 3.026TH FLOOR ELECTRICAL ROOM
 SHOWS NEW TRANSFORMER WHAT
 DOES IT FEED?
 IF THE CHANGE IS ONLY ONE
 TRANSFORMER PLEASE DON'T
 CLOUD WHOLE ROOM TAKES A LONG
 TIME TO FIGURE OUT WHAT THE
 CHANGE IS!!!!!!!!!!
  
 PAGE 4.016TH FLR CHANGE NOT SHOWN ON
 RISER.
  
 NOTE K-8 ??? WHAT SIZE CKT.
 BREAKER IS A 150 HP ???????
  