Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop P
Sequence Number 2
Notes
Date Text
2003-03-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SHT P2.01 VENT REQUIRED FOR FLOOR
 DRAIN IN TRASH ROOM.
 2) ALL UNITS - WET VENTS IN BATHROOMS,
 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDIDIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. (KITCHEN SINKS AND WASH-
 MACHINES SHALL NOT DRAIN THROUGH BATH-
 ROOMS) SECTION 909.1 - THESE CONDITIONS
 SHALL BE CORRECTED ON THE SANITARY RISER
 DIAGRAMS AND ALL FLAT LAYOUTS.
 3) SHT P2.01 RAIN WATER LEADER IS NOT
 SIZED PROPERLY. UNIT 27L
 4) SHT P2.01 PROVIDE AREA BEING DRAINED
 AT TRENCH DRAINS.
 5) SHT P2.01 SECTION 504.7.1 THE DIS-
 CHARGE PIPE SHALL NOT HAVE ANY TRAPPED
 SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP. (RELIEF VALVE FOR HEATER)
 6) SHT P2.01 PROVIDE CALCULATIONS FOR
 CONDENSATE FROM UNITS TO DETERMINE PIPE
 SIZE.
 7) P2.04 4" SANT. AT RISERS 37, 22, 57,
 & 38 SHOWS 4" @ 420 F.U. (MAX 180 F.U.)
 8) SHT P2.04 UNISEX TOILET - NO SANT. TO
 W/C AND LAV.
 9) SHT P2.05 SHOW PIPE SIZE FOR RWL PAST
 TRASH ROOM.
 10) SHT P2.05 SHOW PIPE SIZE FOR COND.
 TO TRASH ROOM.
 11) SHT P2.11 MAX DISTANCE FOR W/C IS 10
 FEET. TABLE 906.1
 12) SHT P2.18 UNIT #3, SHOW PIPE SIZE
 FOR HORIZONTAL RWL. (1900 SQ FT)
 13) SHT P2.19 UNIT B3 SHOW PIPE SIZE FOR
 HORIZONTAL RWL. (2900 SQ FT)
 14) SHT P2.22 UNIT B6, SHOW PIPE SIZE
 FOR HORIZONTAL RWL. (2000 SQ FT)
 15) NEAR UNIT B7, RWL NOT SIZED PROPERLY
 SHOULD BE 890 SQ FT FOR BOTH SIDES. 1980
 SQ FT TOTAL.
 16) SHT P2.31 HORIZONTAL RWL NOT SIZED
 PROPERLY. SHOWS 4" @ 2900 & 2800 SQ FT.
 17) SHT P2.33 UNIT M, 3 DD @ 600 SQ FT
 EACH = 1800 SQ FT. 1500 SQ FT SHOWN.
 PIPE SIZED WRONG.
 18) SHT P2.34 UNIT O, 6" RWL DOWN SHOWS
 600 SQ FT. ADDS UP TO 2900 SQ FT. PLEASE
 ADJUST PLANS.
 19) SHT P2.39 PLEASE SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW ALL AREAS OF ROOFS THAT DRAIN TO
 ROOF FROM ABOVE.SHOW 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPET WALLS.
 INDICATE TOTAL AREA OF MAIN ROOF. SHOW
 LOCATION OF ALL SECONDARY ROOF DRAINS &
 INDICATE AREA BEING DRAINED BY EACH.
 PROVIDE A DETAIL FOR SCUPPERS SHOWING
 LENGTH - WIDTH - HEIGHT - SEE SECTIONS
 1106, 1106.4, 1106.5, 1107, 1107.1,
 1107,2 & 1107.3
 20) SHT P2.44 POOL DECK WATER RISERS,
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 DELETE FROM RISERS.
 21) SHTS P2.40 & P2.41, SHOW TOTAL F.U.
 FOR COMBINED SANITARY RISERS THAT VENT
 THRU ROOF TOGETHER.
 22) SHT P2.44 SHOW PIPE SIZE FOR RWL.
 SHOWS 6" @ 4000 SQ FT. WHEN ADDED IT
 COMES TO 5000 SQ FT AND 6" IS NOT SUFFI-
 CIENT.
 23) SHT P2.45 GARAGE EXHAUST CHASE, WHAT
 WILL BE DRAINING INTO THE FLOOR DRAIN IN
 THE BOTTOM?
 24) SHT P2.45 VENT REQUIRED FOR FLOOR
 DRAIN IN BREEZEWAY DRIVE.
 25) SHT P2.45 VENTS REQUIRED FOR FLOOR
 DRAINS IN TRASH ROOM AND TRASH TERMINA-
 TION ROOM.
 26) SHT P2.49 SQ FOOTAGE NOT CALCULATED
 PROPERLY FOR RWL BY PARKING SPACE 495.
 450 + 220 + 220 = 440 SQ FT ???
 890 + 890 = 1780 SQ FT NOT 1330. 5" PIPE
 IS REQUIRED.
 27) SHT P2.49 MORE INFORMATION REQUIRED
 FOR WATER WALL.
 28) SHTS P3.02, P3.03, P3.04, P3.05,
 P3.06, P3.07 & P3.08 AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE FROM RISERS.
 WATER HAMMER ARRESTORS REQUIRED BY SEC.
 406.9 SHALL BE LOCATED NEAR THE FIXTURE,
 NOT IN CEILING PER PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS. (WASH MACHINE
 ICE MAKER, & DISHWASHER).
 29) SHT P3.09 RWL RISER SHOWS 4" @ 1500
 SQ FT & 4" @ 2900 SQ FT ON SAME RISER.
 PLEASE CLAIRFY.
 30) SHT P3.09 RWL RISER SHOWS 4" @ 1900
 SQ FT ON VERTICAL. BUT RISER ALSO RUNS
 HORIZONTAL, (OFFSET). 5" RISER REQUIRED.
 31) SHT P3.10 RWL BY DECK, NO PIPE SIZE
 SHOWN.
 32) SHT P3.10 RWL RISER SHOWS 5" @ 5100
 SQ FT, BUT RISER ALSO RUNS HORIZONTAL.
 8" RISER REQUIRED.
 33) SHT P3.10 RWL RISER SHOWS 5" @ 3000
 SQ FT PICKING UP 2 ROOF DRAINS. RUNS
 HORIZONTAL, 6" REQUIRED.
 34) SHT P3.10 PIPE SIZE NOT SHOWN FOR
 RWL PIPE IN SOME AREAS.
 35) SHT P3.10 PROVIDE AREA BEING DRAINED
 BY TRENCH DRAINS.
 36) SHT P3.10 RWL RISER SHOWS 6" @ 6900
 SQ FT. RUNS HORIZONTAL, 8" RISER REQD.
 37) SHT P3.10 RWL RISER SHOWS 5" @ 5700
 SQ FT. RUNS HORIZONTAL, 8" RISER REQD.
 38) SHTS P3.11 & P3.12 RELIEF VENTS RE-
 QUIRED AS CONDENSATE EXITS BLDG.
 39) SHT P3.13 FLOOR DRAINS NOT VENTED.
 40) SHTS P3.14 & P3.15 SOIL AND WASTE
 STACKS IN BUILDINGS HAVING MORE THAN 10
 BRANCH INTERVALS SHALL BE PROVIDED WITH
 A RELIEF VENT AT EACH TENTH INTERVAL IN-
 STALLED, BEGINNING WITH THE TOP FLOOR.
 SECTION 914.1
 41) SHTS P3.14/P3.15 HORIZONTAL OFFSETS
 OF DRAINAGE STACKS SHALL BE VENTED WHERE
 FIVE OR MORE BRANCH INTERVALS ARE LOCAT-
 ED ABOVE THE OFFSET. THE OFFSET SHALL BE
 VENTED BY VENTING THE UPPER SECTION OF
 THE DRAINAGE AND THE LOWER SECTION OF
 THE DRAINAGE STACK. SECTION 915.1
 UPPER SECTION SECTION 915.2 LOWER 915.3
 ALSO SEE SECTION 903.4
 42) SHTS P3.14/P3.15 IF A HORIZONTAL
 BRANCH CONNECTS TO THE STACK WITHIN 2 FT
 ABOVE OR BELOW A VERTICAL AND THE OFFSET
 IS LOCATED MORE THAN FOUR BRANCH INTER-V
 ALS BELOW THE TOP OF THE STACK, THE OFF-
 SET SHALL BE VENTED IN ACCORDANCE WITH
 SECTION 915. SECTION 711.1
 43) SHTS P3.14/P3.15 WHEN A HORIZONTAL
 STACK OFFSET IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS BELOW THE TOP OF THE
 STACK, A HORIZONTAL BRANCH SHALL NOT
 CONNECT WITHIN THE HORIZONTAL STACK OFF-
 SET OR WITHIN 2 FEET ABOVE OR BELOW SUCH
 OFFSET. SECTION 711.2 - SEE SECTIONS
 711.3, SECTION 914, 710.1.1, TABLE
 710.1(2) COL 4, SECTION 711.3.1 & SECT-
 ION 711.4.
 44) SHT A5.11 FOUNTAIN EQUIPMENT AREA
 NOT SHOWN ON PLUMBING. MORE INFORMATION
 AND DETAILS REQUIRED.
 45) SHT A5.11A SHOWS POOL EQUIPMENT AREA
 IN THE SAME AREA AS THE FOUNTAIN EQUIP.
 AREA SHT A5.11. PLEASE CLAIRFY.
 46) SHTS A8.01 THRU A8.05 DOOR SHALL NOT
 OPEN INTO THE CLEAR FLOOR SPACE OF ANY
 FIXTURE OR THE 5' TURNING CIRCLE. PLEASE
 CHANGE AS REQUIRED.
 47) SHTS A8.01 THRU A8.05 ALL LIVE/WORK
 LOFTS SHALL HAVE A DRINKING FOUNTAIN PER
 TABLE 403.1. (ALSO SEE 410.1)
 48) SHTS A8.01 THRU A8.14 SHOW CLEAR
 FLOOR SPACE FOR ALL FIXTURES PER FHA
 DESIGN MANUAL PAGE 7.43 & CHAPTER 11 FBC
 49) SHTS A8.12/A8.13 TERRACE DRAINS NOT
 SHOWN ON PLUMBING PLANS. SCUPPER DETAILS
 NOT SHOWN. PLEASE SUBMIT DETAILS AND
 CALL OUT DRAINS ON PLUMBING PLANS.
 50) SHTS A8.13, A8.14, A8.19 THRU A8.39
 PER FHA DESIGN MANUAL, INDICATE SPECI-
 FICATION "A" OR "B" PER REQUIREMENT #7
 FOR ALL UNITS.
 51) SHT A8.26 MENS RESTROOM L106, SHOW
 CLEAR FLOOR SPACE FOR URNAL.
 52) PLEASE SUBMIT ALL SANITARY RISER
 DIAGRAMS. 37 RISERS ARE NOT SHOWN.
 MISSING ARE #'S 8 THRU 10, 12 THRU 15,
 17 THRU 20, 22 THRU 29, 31, 32, 34 THRU
 44, & 55 THRU 59.
 53) PLEASE CONTACT RODNEY COMPO, ENVIRO-
 NMENTAL COMPLIANCE TO SEE IF AN OIL
 SEPARATOR IS REQUIRED FOR TRENCH DRAINS.
 54) SHT A5.16 PLEASE SUBMIT DETAILS FOR
 STEAM ROOM L117.
 55) PLEASE SUBMIT RISERS FOR RELIEF
 VALVE DISCHARGE,(T/P), AND EMERGENCY PAN
 DRAIN LINES FOR WATER HEATERS. INDICATE
 TYPE OF MATERIAL USED AND ALL PIPE SIZE-
 ING. - SHOW THERMAL EXPANSION CONTROL ON
 WATER HEATER DETAIL. SECTION 607.3.2
 56) SHT P6.02 FUEL TANK ROOM, CONTAIN-
 MENT IN CASE OF SPILLAGE?
 57) SEPARATE PLANS & PERMIT REQUIRED FOR
 POOL AND POOL EQUIPMENT ROOM. PLEASE
 ROUTE PLANS TO PALM BEACH HEALTH UNIT
 DIVISION OF ENVIRONMENTAL HEALTH 901
 EVERNIA ST WPB 33401 (561) 355-3018
 58) BACKFLOW REQUIRED FOR SWIMMING POOL
 WATER SERVICE SUPPLY LINE. BACKFLOW RE-
 QUIRED FOR IRRIGATION.
 59) PLEASE PROVIDE DETAILS FOR POOL PUMP
 AND EQUIPMENT ROOM PER SECTION 424.1.5
 AND ALL SUBSECTIONS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
  
  
  
  
  
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 (561) 653-2692 FAX