2003-03-10 00:00:00DENIED:
  
 1.PLAN SHEET M1.02, INDICATES SMOKE
 REMOVAL DUCT TERMINATION.CLARIFY
 DISTANCE TO ANY FRESH AIR OPENINGS, I.E.
 DOORS, WINDOWS, O.A. INTAKES.
  
 2.PLAN SHEET M2.01, EXHAUST DUCT
 PASSING FROM CORRIDOR, BY STAIRS, THRU
 TO BREEZEWAY & UP TO MEZZANINE - NO
 DAMPERS INDICATED.
  
 3.PLAN SHEET M2.02, AHU R/A DUCT
 PENETRATES CORRIDOR WALL LEAVING AHU
 CLOSET & AGAIN GOING BACK INTO THE FOYER
 OF UNIT 16L & 18L, NO FIRE/SMOKE DAMPERS
 INDICATED.
  
 4.SHAFTS THAT ENCLOSE ENVIRONMENTAL
 AIR DUCTS SHALL NOT ENCLOSE ANY OTHER
 TYPE OF DUCTS (NFPA 90A 3-3.4.3).PLAN
 SHEET M2.02 SHOW SUPPLY AIR DUCTS IN THE
 SAME SHAFT AS EXHAUST DUCT, PLEASE
 CLARIFY.
  
 5.PLAN SHEET M2.03, DUCT CONTINUES UP
 TO MEZZANINE NO DUCT SIZE INDICATED.
  
 6.M2.08, O.A. DUCT TO WCACU-L.2-2,
 RATED WALL, NO FIRE DAMPER INDICATED.
  
 7.M2.08 O.A. DUCT, SUPPLY DUCT
 PENETRATES RATED WALL, PLEASE CLARIFY.
  
 8.SEE COMMENT # 3 FOR THE FOLLOWING
 UNITS: 11L, 27, 28, 29, B4, 16L.
  
 9.PLAN SHEET P2.45 INDICATES A FLOOR
 DRAIN IN THE PARKING GARAGE EXHAUST
 SHAFT.EXPLAIN HOW THIS IS GOING TO
 WORK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.