2003-03-10 00:00:00 | DENIED: |
| |
| 1.PLAN SHEET M1.02, INDICATES SMOKE |
| REMOVAL DUCT TERMINATION.CLARIFY |
| DISTANCE TO ANY FRESH AIR OPENINGS, I.E. |
| DOORS, WINDOWS, O.A. INTAKES. |
| |
| 2.PLAN SHEET M2.01, EXHAUST DUCT |
| PASSING FROM CORRIDOR, BY STAIRS, THRU |
| TO BREEZEWAY & UP TO MEZZANINE - NO |
| DAMPERS INDICATED. |
| |
| 3.PLAN SHEET M2.02, AHU R/A DUCT |
| PENETRATES CORRIDOR WALL LEAVING AHU |
| CLOSET & AGAIN GOING BACK INTO THE FOYER |
| OF UNIT 16L & 18L, NO FIRE/SMOKE DAMPERS |
| INDICATED. |
| |
| 4.SHAFTS THAT ENCLOSE ENVIRONMENTAL |
| AIR DUCTS SHALL NOT ENCLOSE ANY OTHER |
| TYPE OF DUCTS (NFPA 90A 3-3.4.3).PLAN |
| SHEET M2.02 SHOW SUPPLY AIR DUCTS IN THE |
| SAME SHAFT AS EXHAUST DUCT, PLEASE |
| CLARIFY. |
| |
| 5.PLAN SHEET M2.03, DUCT CONTINUES UP |
| TO MEZZANINE NO DUCT SIZE INDICATED. |
| |
| 6.M2.08, O.A. DUCT TO WCACU-L.2-2, |
| RATED WALL, NO FIRE DAMPER INDICATED. |
| |
| 7.M2.08 O.A. DUCT, SUPPLY DUCT |
| PENETRATES RATED WALL, PLEASE CLARIFY. |
| |
| 8.SEE COMMENT # 3 FOR THE FOLLOWING |
| UNITS: 11L, 27, 28, 29, B4, 16L. |
| |
| 9.PLAN SHEET P2.45 INDICATES A FLOOR |
| DRAIN IN THE PARKING GARAGE EXHAUST |
| SHAFT.EXPLAIN HOW THIS IS GOING TO |
| WORK. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT 659-8096 |
| EXT. 8388. |