Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-03-14 00:00:001) UNABLE TO LOCATE WRITTEN COMMENTS
 FOR PREVIOUS PLAN REVIEW NOTES
 PROVIDED BY FIRE RESCUE.
  
 2) PLEASE PROVIDE MORE INFORMATION WITH
 REGARDS TO GLASS IN LOBBY DOORS THAT
 ARE PROTECTED WITH A SPRINKLER HEAD ON
 EACH SIDE OF THE GLASS. WATER CURTAINS
 ARE NOT DESIGNED TO PROTECT DOORS.
 PROVIDE RECOGNIZED TEST DATA.
  
 3) ALL EXIT STAIR DOORS SHALL HAVE
 TACTILE SIGNAGE.
  
 4) ALL EXIT STAIRS THAT TERMINATE INTO
 EXIT PASSAGEWAYS SHALL HAVE THE SAME
 FIRE PROTECTION RATING AS THE STAIR.
 PLEASE DEMONSTRATE THIS.
  
 5) THE ORIGNIAL PLANS PROPOSED A 1000
 GPM FIRE PUMP. THIS INFORMATION DOES
 NOT APPEAR TO BE CORRECT. ALL REQUIRED
 STAIRS FOR THE BUILDING SHALL HAVE
 STANDPIPE CONNECTIONS. IF EIGHT STAIRS
 ARE REQUIRED, THEN IN REALITY A 1000
 GPM FIRE PUMP IS NOT LARGE ENOUGH.
 PLEASE ADVISE.
  
 6) PLEASE EXPLAIN GATES AND CARD
 READERS AND HOW DO THEY EFFECT EXITING.
  
 7) PLEASE EXPLAIN OPEN UNPROTECTED
 STAIRS.
  
 8) STAIR # 10 IS NOT IDENTIFIED ON
 STAIR TERMINATION POINT BOX.
  
 9) STAIR # 9 IS NOT IDENTIFIED ON
 STAIR TERMINATION POINT BOX.
  
 10) PLEASE PROVIDE FIRE RATINGS FOR
 STAIR # 10.
  
 11) STAIR # 5 APPEARS TO BE OPEN.
 PLEASE EXPLAIN RATIONALE.
  
 12) HOW DO YOU DIRECT PERSONS VIA
 STAIRS ACROSS AREAS OF PARKING TO
 REACH ENCLOSED EXIT STAIRS.
  
 13) HOW ARE PATHS OF TRAVEL DEFINED ON
 THE LANAI LEVEL.
  
 14) PLEASE EXPLAIN NOTES ON PAGE LS-109
 "GATE AUTOMATICALLY UNLOCKS IN FIRE
 MODE PER FBC 1012.7.
  
 15) MORE DETAILS NEEDED ON ROUND FOAM
 COLUMNS SHOWN ON A3.01.
  
 16) THE KNOX-BOX IS NOTED TO BE
 INSTALLED ON THE INSIDE OF THE BUILDING.
 KNOX-BOXES ARE TO BE INSTALLED ON
 THE EXTERIOR OF THE BUILDING.
  
 17) EXIT ACESS ON MAIN ROOF LEVEL PLAN
 NOTED THRU DEDICATED AREA FOR
 LEASABLE SPACE.
  
 18) EXPANDED POLYSTYRENE NOTED IN
 BUILDING SECTIONS 3 & 3A.
  
 19) PLEASE PROVIDE INFO ON 1" INSULATION
 AROUND TRASH CHUTE.
  
 20) EXIT SIGN MISSING IN CORRIDOR,
 GROUND LEVEL LOBBY AREA ON PAGE E2.01
 TO DIRECT PERSONS TO EXIT BEYOND STAIR
 ENCLOSURE.
  
 21) NO EXIT SIGN SHOWN ON GROUND LEVEL,
 LOBBY AREA II ON PAGE E2.02.
  
 22) NO EXIT SIGNS SHOWN ON GROUND LEVEL,
 LOBBY AREA III ON E2.03.
  
 23) PLEASE EXPLAIN WHY EXITING ON LS 102
 GOES THRU BICYCLE STORAGE AND WHAT
 CODE REFERENCE ALLOWS THIS.
  
 24) ONLY ONE EXIT SIGN SHOWN ON GROUND
 LEVEL LOBBY AREA IV.
  
 25) IT APPEARS THAT DOOR FROM STAIR # 10
 OPENS INTO TENANT STORAGE ROOM A ON
 PAGE E2.10.
  
 26) COULD NOT LOCATE ANY EXIT SIGNS
 IN CORRIDOR ON PAGE E2.12.
  
 27) ONLY ONE EXIT SIGN SHOWN IN CORRIDOR
 ON PAGE E2.13.
  
 28) NO DIRECTIONAL EXIT SIGNS SHOWN
 IN CORRIDOR, TOWER 6TH LEVEL, AREA I
 PAGE E2.19.
  
 29) NO EXIT SIGNS SHOWN IN CORRIDOR
 ON PAGE E2.23.
  
 30) NO EXIT SIGNS SHOWN IN FITNESS
 AREA/YOGA AEROBICS ROOM.
  
 31) EMERGENCY GENERATOR DETAIL INDICATES
 A SUB-BASE FUEL TANK. ROOM IF
 CONTAINING FUEL IS TO BE PROPERLY
 FIRE RATED.
  
 32) SMOKE DETECTORS ARE REQUIRED IN
 EVERY MECHANICAL,ELECTRICAL,TRANSFORMER,
 AND TELEPHONE EQUIPMENT PER 412.2.
  
 33) ONLY ONE EXIT SIGN SHOWN ON PAGE
 E2.49.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910