2003-03-14 00:00:00 | 1) UNABLE TO LOCATE WRITTEN COMMENTS |
| FOR PREVIOUS PLAN REVIEW NOTES |
| PROVIDED BY FIRE RESCUE. |
| |
| 2) PLEASE PROVIDE MORE INFORMATION WITH |
| REGARDS TO GLASS IN LOBBY DOORS THAT |
| ARE PROTECTED WITH A SPRINKLER HEAD ON |
| EACH SIDE OF THE GLASS. WATER CURTAINS |
| ARE NOT DESIGNED TO PROTECT DOORS. |
| PROVIDE RECOGNIZED TEST DATA. |
| |
| 3) ALL EXIT STAIR DOORS SHALL HAVE |
| TACTILE SIGNAGE. |
| |
| 4) ALL EXIT STAIRS THAT TERMINATE INTO |
| EXIT PASSAGEWAYS SHALL HAVE THE SAME |
| FIRE PROTECTION RATING AS THE STAIR. |
| PLEASE DEMONSTRATE THIS. |
| |
| 5) THE ORIGNIAL PLANS PROPOSED A 1000 |
| GPM FIRE PUMP. THIS INFORMATION DOES |
| NOT APPEAR TO BE CORRECT. ALL REQUIRED |
| STAIRS FOR THE BUILDING SHALL HAVE |
| STANDPIPE CONNECTIONS. IF EIGHT STAIRS |
| ARE REQUIRED, THEN IN REALITY A 1000 |
| GPM FIRE PUMP IS NOT LARGE ENOUGH. |
| PLEASE ADVISE. |
| |
| 6) PLEASE EXPLAIN GATES AND CARD |
| READERS AND HOW DO THEY EFFECT EXITING. |
| |
| 7) PLEASE EXPLAIN OPEN UNPROTECTED |
| STAIRS. |
| |
| 8) STAIR # 10 IS NOT IDENTIFIED ON |
| STAIR TERMINATION POINT BOX. |
| |
| 9) STAIR # 9 IS NOT IDENTIFIED ON |
| STAIR TERMINATION POINT BOX. |
| |
| 10) PLEASE PROVIDE FIRE RATINGS FOR |
| STAIR # 10. |
| |
| 11) STAIR # 5 APPEARS TO BE OPEN. |
| PLEASE EXPLAIN RATIONALE. |
| |
| 12) HOW DO YOU DIRECT PERSONS VIA |
| STAIRS ACROSS AREAS OF PARKING TO |
| REACH ENCLOSED EXIT STAIRS. |
| |
| 13) HOW ARE PATHS OF TRAVEL DEFINED ON |
| THE LANAI LEVEL. |
| |
| 14) PLEASE EXPLAIN NOTES ON PAGE LS-109 |
| "GATE AUTOMATICALLY UNLOCKS IN FIRE |
| MODE PER FBC 1012.7. |
| |
| 15) MORE DETAILS NEEDED ON ROUND FOAM |
| COLUMNS SHOWN ON A3.01. |
| |
| 16) THE KNOX-BOX IS NOTED TO BE |
| INSTALLED ON THE INSIDE OF THE BUILDING. |
| KNOX-BOXES ARE TO BE INSTALLED ON |
| THE EXTERIOR OF THE BUILDING. |
| |
| 17) EXIT ACESS ON MAIN ROOF LEVEL PLAN |
| NOTED THRU DEDICATED AREA FOR |
| LEASABLE SPACE. |
| |
| 18) EXPANDED POLYSTYRENE NOTED IN |
| BUILDING SECTIONS 3 & 3A. |
| |
| 19) PLEASE PROVIDE INFO ON 1" INSULATION |
| AROUND TRASH CHUTE. |
| |
| 20) EXIT SIGN MISSING IN CORRIDOR, |
| GROUND LEVEL LOBBY AREA ON PAGE E2.01 |
| TO DIRECT PERSONS TO EXIT BEYOND STAIR |
| ENCLOSURE. |
| |
| 21) NO EXIT SIGN SHOWN ON GROUND LEVEL, |
| LOBBY AREA II ON PAGE E2.02. |
| |
| 22) NO EXIT SIGNS SHOWN ON GROUND LEVEL, |
| LOBBY AREA III ON E2.03. |
| |
| 23) PLEASE EXPLAIN WHY EXITING ON LS 102 |
| GOES THRU BICYCLE STORAGE AND WHAT |
| CODE REFERENCE ALLOWS THIS. |
| |
| 24) ONLY ONE EXIT SIGN SHOWN ON GROUND |
| LEVEL LOBBY AREA IV. |
| |
| 25) IT APPEARS THAT DOOR FROM STAIR # 10 |
| OPENS INTO TENANT STORAGE ROOM A ON |
| PAGE E2.10. |
| |
| 26) COULD NOT LOCATE ANY EXIT SIGNS |
| IN CORRIDOR ON PAGE E2.12. |
| |
| 27) ONLY ONE EXIT SIGN SHOWN IN CORRIDOR |
| ON PAGE E2.13. |
| |
| 28) NO DIRECTIONAL EXIT SIGNS SHOWN |
| IN CORRIDOR, TOWER 6TH LEVEL, AREA I |
| PAGE E2.19. |
| |
| 29) NO EXIT SIGNS SHOWN IN CORRIDOR |
| ON PAGE E2.23. |
| |
| 30) NO EXIT SIGNS SHOWN IN FITNESS |
| AREA/YOGA AEROBICS ROOM. |
| |
| 31) EMERGENCY GENERATOR DETAIL INDICATES |
| A SUB-BASE FUEL TANK. ROOM IF |
| CONTAINING FUEL IS TO BE PROPERLY |
| FIRE RATED. |
| |
| 32) SMOKE DETECTORS ARE REQUIRED IN |
| EVERY MECHANICAL,ELECTRICAL,TRANSFORMER, |
| AND TELEPHONE EQUIPMENT PER 412.2. |
| |
| 33) ONLY ONE EXIT SIGN SHOWN ON PAGE |
| E2.49. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |