Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop E
Sequence Number 2
Notes
Date Text
2003-03-11 00:00:00****************** UNSAT ************
  
 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULES
 PER 210-12
  
 2)NOTE: PLEASE SEE MISSING FINAL LOAD
 ON APT 28 PANEL.
  
 3)NOTE: PLEASE PROVIDE GROUNDING DETAIL
 ON RISER DIAGRAM. PLEASE INCLUDE BLDG/
 FOOTER STEEL, COLD WATER. 250-50
  
 4)NOTE: PLEASE NOTE, MANY PAGES REFER
 TO PAGE E4.06 AND THIS PAGE WAS NOT
 SUBMITTED.?
 IT APPEARS PLANS SHOW A FPL VAULT ON
 EVERY OTHER FLOOR??
 PLEASE CLARIFY?
 ALL MAINS FOR BLDG ARE TO BE GROUPED
 PER 230-72.ALSO 230-70/230-2
 SHUNT TRIPS ARE NOT RATED FOR MEANS OF
 DISCONNECT. PLEASE SEE 230-76/230-79.
 IT IS SHOWN IN FIRE CONTROL ROOM, SHUNT
 TRIPS FOR METER CENTERS.
 PLEASE SEE THIS IS NOT PERMITTED. PLEASE
 SEE ABOVE NOTES PER NEC AND ALSO PER
 LOCAL FIRE MARSHALLS OFFICE. ALL MAINS
 ARE TO BE GROUPED IN CLOSE PROXIMITY.
  
 5)NOTE: PLEASE SEE RISER, SHOWS DP REH
 FEEDING PANEL DP REL. PLEASE SEE 5.14
 PANEL SCHEDULE FOR DP_REL IS MISSING
 COMPLETED INFORMATION FOR DP REL?
 PLANS SEEM TO BE MISSING DP REL PANEL
 SCHEDULE?
  
 6)NOTE: PLEASE CLARIFY GFI PROTECTION
 FOR 3000A MAIN? 230-95/240-13
 PLEASE ALSO NOTE ON PLANS FOR REQ`MENTS
 OF 230-203
  
 7)NOTE: PLEASE PROVIDE NOTE FOR VERTICAL
 CONDUCTOR SUPPORT PER 300-19
  
 8)NOTE: PLEASE PROVIDE INFORMATION/SPECS
 FOR FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE 695-4/695-4-B1/ 695-5
 PLEASE ALSO PROVIDE CODE LETTER INFOR-
 -MATION SET ON NAMEPLATE. PLEASE SEE
 TABLES UNDER 430
  
 9)NOTE: PLEASE CORRELATE KW RATING OF
 GENERATOR. RISER SHOWS 900KW/750KVA
 AND 3.01 SHOWS 750KW?
  
 10)NOTE: PLEASE CORRELATE CONDUIT FOR
 FIRE PUMP. RISER SHOWS ONE-2 1/2"
 CONDUIT AND 1.0 SHOWS 4"?.
  
 11)NOTE:PLEASE PROVIDE NOTED INFORMATION
 FOR FIXTURES THAT ARE REQ`D FOR
 EMERGENCY ILLUMINATION TO MEET 700-16.
 PLEASE SEE FIRE PUMP ROOM AND OTHER
 LOCATIONS.
  
 12)NOTE: PLEASE SHOW OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED. PER 210-8-A6
  
 13)NOTE: AS PER 240-24E PANELS ARE NOT
 TO BE LOCATED IN BATHROOMS. (2.01)
  
 14)NOTE: PLEASE PROVIDE/CLARIFY WHERE
 CAN LIGHTING FOR OUTSIDE OF BLDG BE
 FOUND? PLEASE CLARIFY HOW 210-70 IS MET?
  
 15)NOTE: PLEASE COMPLETE APT/UNIT LAYOUT
 -S. SOME PAGES REFER OTHER PAGES AND
 THERE IS NOTHING ON THOSE PAGES TO
 CORRELATE NOTE?? THIS WAS NOTED ON
 FIRST REVIEW ALSO. PLEASE SEE PAGE #`S
  
 16)NOTE: PLEASE CLARIFY WHAT APPEARS TO
 BE AN ISLAND IN UNIT 12L? AND ANY OTHERS
 PLEASE SEE 210-52-C-2
  
 17)NOTE: PLEASE SEE MANY OTHER UNITS
 SHOWING TWO PANELS??
  
 18)NOTE: PLEASE SEE AREA WHERE LOFTS/
 MEZZ LEVEL RAILS ARE. RECEPT SPACING IS
 STILL REQ`D TO MEET 210-52
 RAILS ARE CONSIDERED WALL SPACE.
  
 19)NOTE: SIGNAGE REQ`D FOR ALL ELEC-
 -TTRICAL ROOMS.
  
 20)NOTE: PLEASE SEE 210-52-C1 FOR
 SPACING OF COUNTERSPACE RECEPTS.
  
 21)NOTE: PLEASE SEE PLANS, SOME UNITS
 MISSING SD`S ON 2ND LEVELS.
  
 22)NOTE: PLEASE SEE PLANS, SOME UNITS
 ARE MISSING RECEPTS FOR WALL SPACING
 2'/6'/12'. 210-52
  
 23)NOTE: PLEASE SEE G-1 ON 2.31,
 PLEASE CLARIFY 4-5 HORN/SROBES IN
 BEDROOM??
  
 24)NOTE: PLEASE SEE PANEL UNIT N ON
 2.32 SHOWN FACING INTO BATHRROM RECEPT??
 110-26 ETC.
  
 25)NOTE: PLEASE SHOW SERVICE RECEPTS
 ON ROOF 210-63
  
 26)NOTE: NOT ENOUGH INFORMATION FOR
 POOL AREA. PLEASE SUBMIT FOR MIN REQ`
 -MENTS.
  
 PLEASE NOTE, THIS IS THE SECOND TIME
 PLANS HAVE BEEN REVIEWD FOR THIS PROJECT
 PLEASE SEE FS/FAC 553-80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS.
  
 PLEASE ALSO NOTE, MANY COMMENTS ABOVE
 PERTAIN TO MORE THAN ONE SHEET AND/OR
 PAGE. PLEASE GO OVER ENTIRE SET BEFORE
 RESUBMITTING.
  
 PLEASE ADDRESS AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL. IF A MEETING
 IS DESIRED TO GO OVER COMMENTS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372