2003-03-11 00:00:00 | ****************** UNSAT ************ |
| |
| 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROTECTED CIRCUITS ON PANEL SCHEDULES |
| PER 210-12 |
| |
| 2)NOTE: PLEASE SEE MISSING FINAL LOAD |
| ON APT 28 PANEL. |
| |
| 3)NOTE: PLEASE PROVIDE GROUNDING DETAIL |
| ON RISER DIAGRAM. PLEASE INCLUDE BLDG/ |
| FOOTER STEEL, COLD WATER. 250-50 |
| |
| 4)NOTE: PLEASE NOTE, MANY PAGES REFER |
| TO PAGE E4.06 AND THIS PAGE WAS NOT |
| SUBMITTED.? |
| IT APPEARS PLANS SHOW A FPL VAULT ON |
| EVERY OTHER FLOOR?? |
| PLEASE CLARIFY? |
| ALL MAINS FOR BLDG ARE TO BE GROUPED |
| PER 230-72.ALSO 230-70/230-2 |
| SHUNT TRIPS ARE NOT RATED FOR MEANS OF |
| DISCONNECT. PLEASE SEE 230-76/230-79. |
| IT IS SHOWN IN FIRE CONTROL ROOM, SHUNT |
| TRIPS FOR METER CENTERS. |
| PLEASE SEE THIS IS NOT PERMITTED. PLEASE |
| SEE ABOVE NOTES PER NEC AND ALSO PER |
| LOCAL FIRE MARSHALLS OFFICE. ALL MAINS |
| ARE TO BE GROUPED IN CLOSE PROXIMITY. |
| |
| 5)NOTE: PLEASE SEE RISER, SHOWS DP REH |
| FEEDING PANEL DP REL. PLEASE SEE 5.14 |
| PANEL SCHEDULE FOR DP_REL IS MISSING |
| COMPLETED INFORMATION FOR DP REL? |
| PLANS SEEM TO BE MISSING DP REL PANEL |
| SCHEDULE? |
| |
| 6)NOTE: PLEASE CLARIFY GFI PROTECTION |
| FOR 3000A MAIN? 230-95/240-13 |
| PLEASE ALSO NOTE ON PLANS FOR REQ`MENTS |
| OF 230-203 |
| |
| 7)NOTE: PLEASE PROVIDE NOTE FOR VERTICAL |
| CONDUCTOR SUPPORT PER 300-19 |
| |
| 8)NOTE: PLEASE PROVIDE INFORMATION/SPECS |
| FOR FIRE PUMP AND FIRE PUMP CONTROLLER. |
| PLEASE SEE 695-4/695-4-B1/ 695-5 |
| PLEASE ALSO PROVIDE CODE LETTER INFOR- |
| -MATION SET ON NAMEPLATE. PLEASE SEE |
| TABLES UNDER 430 |
| |
| 9)NOTE: PLEASE CORRELATE KW RATING OF |
| GENERATOR. RISER SHOWS 900KW/750KVA |
| AND 3.01 SHOWS 750KW? |
| |
| 10)NOTE: PLEASE CORRELATE CONDUIT FOR |
| FIRE PUMP. RISER SHOWS ONE-2 1/2" |
| CONDUIT AND 1.0 SHOWS 4"?. |
| |
| 11)NOTE:PLEASE PROVIDE NOTED INFORMATION |
| FOR FIXTURES THAT ARE REQ`D FOR |
| EMERGENCY ILLUMINATION TO MEET 700-16. |
| PLEASE SEE FIRE PUMP ROOM AND OTHER |
| LOCATIONS. |
| |
| 12)NOTE: PLEASE SHOW OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| ED. PER 210-8-A6 |
| |
| 13)NOTE: AS PER 240-24E PANELS ARE NOT |
| TO BE LOCATED IN BATHROOMS. (2.01) |
| |
| 14)NOTE: PLEASE PROVIDE/CLARIFY WHERE |
| CAN LIGHTING FOR OUTSIDE OF BLDG BE |
| FOUND? PLEASE CLARIFY HOW 210-70 IS MET? |
| |
| 15)NOTE: PLEASE COMPLETE APT/UNIT LAYOUT |
| -S. SOME PAGES REFER OTHER PAGES AND |
| THERE IS NOTHING ON THOSE PAGES TO |
| CORRELATE NOTE?? THIS WAS NOTED ON |
| FIRST REVIEW ALSO. PLEASE SEE PAGE #`S |
| |
| 16)NOTE: PLEASE CLARIFY WHAT APPEARS TO |
| BE AN ISLAND IN UNIT 12L? AND ANY OTHERS |
| PLEASE SEE 210-52-C-2 |
| |
| 17)NOTE: PLEASE SEE MANY OTHER UNITS |
| SHOWING TWO PANELS?? |
| |
| 18)NOTE: PLEASE SEE AREA WHERE LOFTS/ |
| MEZZ LEVEL RAILS ARE. RECEPT SPACING IS |
| STILL REQ`D TO MEET 210-52 |
| RAILS ARE CONSIDERED WALL SPACE. |
| |
| 19)NOTE: SIGNAGE REQ`D FOR ALL ELEC- |
| -TTRICAL ROOMS. |
| |
| 20)NOTE: PLEASE SEE 210-52-C1 FOR |
| SPACING OF COUNTERSPACE RECEPTS. |
| |
| 21)NOTE: PLEASE SEE PLANS, SOME UNITS |
| MISSING SD`S ON 2ND LEVELS. |
| |
| 22)NOTE: PLEASE SEE PLANS, SOME UNITS |
| ARE MISSING RECEPTS FOR WALL SPACING |
| 2'/6'/12'. 210-52 |
| |
| 23)NOTE: PLEASE SEE G-1 ON 2.31, |
| PLEASE CLARIFY 4-5 HORN/SROBES IN |
| BEDROOM?? |
| |
| 24)NOTE: PLEASE SEE PANEL UNIT N ON |
| 2.32 SHOWN FACING INTO BATHRROM RECEPT?? |
| 110-26 ETC. |
| |
| 25)NOTE: PLEASE SHOW SERVICE RECEPTS |
| ON ROOF 210-63 |
| |
| 26)NOTE: NOT ENOUGH INFORMATION FOR |
| POOL AREA. PLEASE SUBMIT FOR MIN REQ` |
| -MENTS. |
| |
| PLEASE NOTE, THIS IS THE SECOND TIME |
| PLANS HAVE BEEN REVIEWD FOR THIS PROJECT |
| PLEASE SEE FS/FAC 553-80(2)(B) WITH |
| RESPECT TO DESIGN PROFESSIONALS. |
| |
| PLEASE ALSO NOTE, MANY COMMENTS ABOVE |
| PERTAIN TO MORE THAN ONE SHEET AND/OR |
| PAGE. PLEASE GO OVER ENTIRE SET BEFORE |
| RESUBMITTING. |
| |
| PLEASE ADDRESS AND SUBMIT THE ABOVE |
| INFORMATION FOR REVIEW. IF THERE ARE |
| ANY QUESTIONS, PLEASE CALL. IF A MEETING |
| IS DESIRED TO GO OVER COMMENTS, PLEASE |
| CALL. |
| |