2003-03-07 00:00:00 | PAID PLAN REVIEW, NOT A PERMIT |
| APPLICATION. |
| |
| AT TIME OF PERMIT APPLICATION, THE |
| ENERGY CODE CALCULATIONS ARE REQUIRED |
| TO BE SIGNED, DATED AND SEALED BY THE |
| PREPARER. FBC 13-103.1 |
| |
| COMPLETE SPECIFICATIONS HAVE NOT BEEN |
| PROVIDED, THEY WILL BE NECESSARY FOR |
| THE PERMIT APPLICATION.SEE FBC 104.2.1 |
| |
| CONCURRENT WITH THE PERMIT APPLICATION |
| COMPLIANCE WITH FBC 1803.1.3 AND 1803.2 |
| MUST BE DEMONSTRATED. |
| |
| ITEM #6 UNDER BUILDING CODE INFO ON |
| SHEET LS 1.00 DECLARES FIRE RATING |
| REDUCTIONS APPLIED.SEE FBC TABLE 600 |
| FOOTNOTE (L) FORTHE LIMITATIONS. |
| EXTERIOR WALLS, SHAFT ENCLOSURES AND |
| OCCUPANCY SEPARATIONS ARE NOT INCLUDED. |
| |
| SHEET LS NOTE 9 SPEAKS TO GLASS IN DOORS |
| HAVING A SPRINKLER ON EACH SIDE. |
| OPENING PROTECTIVES MUST COMPLY WITH |
| FBC 705. |
| |
| NOTE 8 ON LS 1.00 IMPLIES AND IMPROPER |
| APPLICATION OF FBC TABLE 600. |
| HORIZONTAL MEASUREMENTS ARE FROM THE |
| WALL PLANE AND VERTICAL MEASUREMENTS |
| ARE PER FLOOR, FROM FINISH FLOOR TO |
| CEILING ABOVE. |
| |
| NOTE 18 SPEAKS TO FOAM MOLDINGS. |
| ARCHITECTURAL TRIM IS REQUIRED TO BE |
| NON-COMBUSTIBLE OR FRT WOOD.SEE FBC |
| F102.2.7 AS AMENDED BY THE CITY AND FBC |
| 1404. |
| |
| SEVERAL OF THE MEZZANINE UNITS SHOW A |
| TRAVEL DISTANCE >75'. FBC 1005.7.1 |
| REQUIRES TWO MEANS OF EGRESS COMPLYING |
| WITH FBC 1004.1.4. |
| |
| THE STAIRS SHOWN AS #5, #7 AND #10 DO |
| NOT COMPLY WITH FBC 1006.1.1 AND FBC |
| 412.11 #5. |
| |
| SHEET A11.05. IF THE HC PARKING SPACES |
| SERVICE THE GROUP "B" LIVE WORK LOFT |
| THEY MUST BE 12' WIDE IN ACCORDANCE |
| WITH FBC 11-4.6 INCLUDING THE 98" |
| VERTICAL CLEARANCE. |
| |
| SHEET A6.05 SHOWS POLYSTYRENE TO VE |
| USEDFOR EXTERIOR TRIM.THIS IS |
| PROHIBITED BY FBC F102.2.7 (AMENDED) |
| FBC 1404 |
| |
| SHEET A11.01, SHOW A SPECIFIC FRAMING |
| AND FASTENING DETAIL FOR THE SUSPENDED |
| GYP BOARD CEILINGS. FBC 104.2. |
| |
| THE WALL SHOWN AS W19 ON SHEET S-32 IS |
| ABERING WALL AND IS REQUIRED TO BE FIRE |
| RATED.SEE FBC TABLE 600. |
| |
| THE WIND TUNNEL TEST REPORT EXCLUDES |
| THE ROOF TILE FROM ITS FINDINGS. |
| PROVIDE THE NECESSARY INFORMATION IN |
| ACCORDANCE WITH FBC 104.2.1.1. |