Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop P
Sequence Number 13
Notes
Date Text
2004-08-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) NUMEROUS SHEETS SHOW NOT CHANGES FROM
 THE LAST REVISION OR SINCE THE PLANS
 WERE STAMPED. PLEASE DELETE ALL SHEETS
 THAT HAVE NOT REVISION TO REVIEW. SECT-
 ION 104.2.1
 2) SHTS P2.01 & P3.13 RISER DIAGRAM DOES
 NOT REFLECT FLOOR PLAN. RISERS DOWN-
 STREAM OF 5" @ 302 FU SHOW 3" 4FU THEN
 2" 2FU ON FLOOR PLAN BUT RISER SHOWS THE
 2" 2FU & 3" 4FU IN REVERSE ORDER. THIS
 IS SHOWN AT 3 DIFFERENT AREAS. PLEASE
 CORRELATE PLANS. SECTION 104.2.1
 3) SHT P301 AIR CHAMBERS ARE NOT APPROV-
 ED IN MEN'S AND WOMEN'S BATHROOMS, AND
 A WATER HAMMER ARRESTOR IS REQUIRED AT
 THE DISH WASHER ON RISER FOR MEN'S BATH-
 ROOM. SECTION 604.9
 4) SHT P3.05 UNIT 25 WATER RISER DOES
 NOT REFLECT THE FLOOR PLAN ON SHT P2.16
 NO WATER SUPPLY SHOWN TO SHOWER.
 5) SHT P3.05 UNITS 1, 25, 28, & 38 WATER
 RISER DIAGRAMS. WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE DISH WASHER & ICE
 MAKER IN THE REFRIG. SECTION 604.9
 6) SHT P3.18 RISER 27/30 2ND/4TH FLOOR
 ISLAND VENT NOT APPROVED. VENT LINE
 SHOWN TIED BACK INTO THE VENT FROM THE
 ISLAND VENT IS A HORIZONTAL DRY VENT AND
 NOT APPROVED. SECTION 905.3
  