2004-08-16 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| 1) NUMEROUS SHEETS SHOW NOT CHANGES FROM |
| THE LAST REVISION OR SINCE THE PLANS |
| WERE STAMPED. PLEASE DELETE ALL SHEETS |
| THAT HAVE NOT REVISION TO REVIEW. SECT- |
| ION 104.2.1 |
| 2) SHTS P2.01 & P3.13 RISER DIAGRAM DOES |
| NOT REFLECT FLOOR PLAN. RISERS DOWN- |
| STREAM OF 5" @ 302 FU SHOW 3" 4FU THEN |
| 2" 2FU ON FLOOR PLAN BUT RISER SHOWS THE |
| 2" 2FU & 3" 4FU IN REVERSE ORDER. THIS |
| IS SHOWN AT 3 DIFFERENT AREAS. PLEASE |
| CORRELATE PLANS. SECTION 104.2.1 |
| 3) SHT P301 AIR CHAMBERS ARE NOT APPROV- |
| ED IN MEN'S AND WOMEN'S BATHROOMS, AND |
| A WATER HAMMER ARRESTOR IS REQUIRED AT |
| THE DISH WASHER ON RISER FOR MEN'S BATH- |
| ROOM. SECTION 604.9 |
| 4) SHT P3.05 UNIT 25 WATER RISER DOES |
| NOT REFLECT THE FLOOR PLAN ON SHT P2.16 |
| NO WATER SUPPLY SHOWN TO SHOWER. |
| 5) SHT P3.05 UNITS 1, 25, 28, & 38 WATER |
| RISER DIAGRAMS. WATER HAMMER ARRESTORS |
| ARE REQUIRED AT THE DISH WASHER & ICE |
| MAKER IN THE REFRIG. SECTION 604.9 |
| 6) SHT P3.18 RISER 27/30 2ND/4TH FLOOR |
| ISLAND VENT NOT APPROVED. VENT LINE |
| SHOWN TIED BACK INTO THE VENT FROM THE |
| ISLAND VENT IS A HORIZONTAL DRY VENT AND |
| NOT APPROVED. SECTION 905.3 |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |