Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop B
Sequence Number 10
Notes
Date Text
2004-02-23 00:00:00***CORRECTIONS***
  
 REVISIONS 12 THROUGH 17B, VARIOUS DATES
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)WHAT IS THE USE OF THE NEW ROOM
 BEING CREATED ABOVE THE TRASH CHUTE
 ROOM, AND HOW WILL THAT ROOM BE
 ACCESSED? (A7.06)
  
 2.)CHUTE PROTECTION REQUIRED, SECTIONS
 10 AND 3, A7.06.
  
 3.)WHAT TRANSPIRED BETWEEN REVISIONS
 13 AND 17B?
  
 4.)ACCESSIBLE PARKING SPACES SHALL BE
 LEVEL WITH SURFACE SLOPES NOT EXCEEDING
 1:50 (PLAN SHOWS 1/4"/FT), FBC11-4.6.3.
  
 5.)WHERE CHANGES IN ELEVATION OF 12"
 OR LESS OCCUR IN EXITS, RAMPS COMPLYING
 WITH FBC1013 SHALL BE PROVIDED, SHEET
 A7.11 (2-A7.11) SHOWS A 6" CHANGE IN
 ELEVATION.
  
 6.)PROVIDE INFORMATION REGARDING THE
 ATTACHMENT FOR THE STONE BASE AND WALL
 PANELS SHOWN ON A8.03.
  
 7.)SHEET 11.08 STILL HAS REFERENCES TO
 FOAM MOLDINGS (THERE IS A NOTE
 INDICATING THAT ALL MOLDINGS WILL BE
 STONE).
  
 8.)THE ARCHITECTURE FIRM LICENSE
 NUMBER AND PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS REQUIRED TO BE
 ON EACH SHEET, FAC61G1-16.004.
  
 CC:DON NEELY