2002-05-10 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| |
| 1) PLANS ARE NOT COMPLETE FOR SUFFICIENT |
| REVIEW. MORE INFORMATION IS REQUIRED FOR |
| COMPLETE REVIEW. |
| 2) SHT P1.01 OIL INTERCEPTORS, PLEASE |
| CONTACT RODNEY COMPO ENVIRONMENTAL COM- |
| PLIANCE FOR SIZE OF OIL INTERCEPTORS |
| (561) 837-4074.(SHT P1.05 ALSO) |
| 3) SHT P1.05 NOT SANITARY SHOWN FOR |
| POWDER ROOM. |
| 4) SHT P1.07 BATH B2 NO SANITARY SHOWN |
| TO WATER CLOSET. |
| 5) SHT P1.26 M/BATH UNIT K NO SANT TO |
| TUB. |
| 6) SHT P1.28 SHOWS STEAM SAUNA IN MENS |
| ROOM AND URNAL IN WOMENS ROOM ??? |
| 7) SHT P1.40 BATHROOM B2 BY STAIR #4 TUB |
| NOT VENTED PROPERLY |
| 8) SHT P1.42 RISER #5 W/C NOT VENTED. |
| 9) SHT UNIT R WASH MACHINE SHALL NOT |
| DRAIN INTO BATHROOM GROUP. |
| 10) SHT P1/47 TUB NOT VENTED UNIT T |
| 11) SHT P1.56 RISERS ARE INCOMPLETE. |
| PLEASE IDENTIFY EACH RISER. RELIEF VENT |
| NOT SHOWN ON RISERS |
| 12) PLEASE SUBMIT RISER DIAGRAMS FOR |
| STORM, WATER, CONDENSATE, RELIEF VALVE - |
| (P/T) DISCHARGE, & EMERGENCY PAN DRAIN. |
| ALSO GIVE A COMPLETE RISER DIAGRAM ISO- |
| METRIC SHOWING COMPLETE SYSTEMS WITH |
| HORIZONTAL PIPING, PIPE SIZE FIXTURE UN- |
| IT LOADS AS THEY ACCUMULATE AT EACH RIS- |
| ER ALL THE WAY OUT OF BLDG. |
| 13) SHOW ALL OFFSETS FOR EACH SANITARY R |
| ISERS AND INDICATE IF VERITCAL OR HORIZ- |
| ONTAL OFFSETS. |
| 14) VENTS NOT SHOWN THRU ROOF. |
| 15) SHT 1.64 LANAI ROOF - WHAT IS THE |
| DESIGNATION PR REFER TO? NOT ALL PIPES |
| ARE SIZED. |
| 16) SHT A1.05 TRANSFORMER VAULT, IS SUMP |
| TO BE PIPED OR JUST FOR CONTAINMENT OF |
| OILS IN CASE OF EMERGENCY? |
| 17) SHT A1.05 GARAGE EXHAUST AND AIR |
| SUPPLY FLOOR DRAINS, TO STORM? WILL FIRE |
| AND DOMESTIC PUMP RMS HAVE FLOOR DRAINS? |
| 18) SHT A1.05 FUEL TANK ROOM, CONTAIN- |
| MENT IN CASE OF SPILLAGE? |
| 19) PLEASE SUBMIT CALCULATIONS FOR ALL |
| PRIMARY AND SECONDARY ROOF DRAINS. ADD |
| ALL AREAS OF ROOF THAT DRAIN FROM ABOVE |
| AND 1/2 ALL AREA OF ALL VERTICAL WALLS. |
| SHOW LOCATION OF ALL SECONDARY ROOF |
| DRAINS. CALCULATE PER FBC PLMB SEC 1106 |
| & 1107, TABLES 1106.2, & 1106.3, FIGURE |
| 1106.1. |
| 20) PLEASE INDICATE MATERIALS USED FOR |
| ALL PLUMBING SYSTEMS. |
| 21) PLEASE SHOW BACKFLOWS REQUIRED FOR |
| MAKE UP WATER TO COOLING TOWERS, SWIMM- |
| ING POOL, & IRRIGATION. PLEASE INDICATE |
| MANUFACTURE AND MODEL NUMBER, AND LOCAT- |
| ION OF EACH. |
| 22) SEPARATE PLANS AND PERMIT REQUIRED |
| FOR POOL, & POOL EQUIPMENT ROOM. PLEASE |
| ROUTE PLANS TO PALM BEACH HEALTH UNIT |
| DIVISION OF ENVIRONMENTAL HEALTH 901 |
| EVERNIA STREET, WPB FL 33401 (561) 355- |
| 3018. |
| 23) PLEASE SUBMIT DETAILS FOR SAUNA AND |
| STEAM ROOMS |
| 24) PLEASE SUBMIT WATER HEATER DETAILS. |
| PROVIDE INFORMATION FOR SEC 504.7.1, THE |
| DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP- |
| ED SECTIONS AND SHALL HAVE A VISIBLE AIR |
| GAP OR AIR GAP FITTING LOCATED IN THE |
| SAME ROOM AS HEATER. SUBMIT INFO FOR |
| THERMAL EXPANSION CONTROL, 607.3 |
| 25) SHT A8.22 PLEASE SHOW CLEAR FLOOR |
| SPACE FOR URNAL. (30"X48" MINIMUM) |
| 26) SHTS A8.33/A8.34 UNIT Q, FIREPLACE |
| PLEASE SUBMIT DETAILS. SHOW EXHAUST DUCT |
| IS THIS A GAS FIREPLACE? |
| |
| REVIEW BY KEN STEVENS |