2002-05-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PLANS ARE NOT COMPLETE FOR SUFFICIENT
 REVIEW. MORE INFORMATION IS REQUIRED FOR
 COMPLETE REVIEW.
 2) SHT P1.01 OIL INTERCEPTORS, PLEASE
 CONTACT RODNEY COMPO ENVIRONMENTAL COM-
 PLIANCE FOR SIZE OF OIL INTERCEPTORS
 (561) 837-4074.(SHT P1.05 ALSO)
 3) SHT P1.05 NOT SANITARY SHOWN FOR
 POWDER ROOM.
 4) SHT P1.07 BATH B2 NO SANITARY SHOWN
 TO WATER CLOSET.
 5) SHT P1.26 M/BATH UNIT K NO SANT TO
 TUB.
 6) SHT P1.28 SHOWS STEAM SAUNA IN MENS
 ROOM AND URNAL IN WOMENS ROOM ???
 7) SHT P1.40 BATHROOM B2 BY STAIR #4 TUB
 NOT VENTED PROPERLY
 8) SHT P1.42 RISER #5 W/C NOT VENTED.
 9) SHT UNIT R WASH MACHINE SHALL NOT
 DRAIN INTO BATHROOM GROUP.
 10) SHT P1/47 TUB NOT VENTED UNIT T
 11) SHT P1.56 RISERS ARE INCOMPLETE.
 PLEASE IDENTIFY EACH RISER. RELIEF VENT
 NOT SHOWN ON RISERS
 12) PLEASE SUBMIT RISER DIAGRAMS FOR
 STORM, WATER, CONDENSATE, RELIEF VALVE -
 (P/T) DISCHARGE, & EMERGENCY PAN DRAIN.
 ALSO GIVE A COMPLETE RISER DIAGRAM ISO-
 METRIC SHOWING COMPLETE SYSTEMS WITH
 HORIZONTAL PIPING, PIPE SIZE FIXTURE UN-
 IT LOADS AS THEY ACCUMULATE AT EACH RIS-
 ER ALL THE WAY OUT OF BLDG.
 13) SHOW ALL OFFSETS FOR EACH SANITARY R
 ISERS AND INDICATE IF VERITCAL OR HORIZ-
 ONTAL OFFSETS.
 14) VENTS NOT SHOWN THRU ROOF.
 15) SHT 1.64 LANAI ROOF - WHAT IS THE
 DESIGNATION PR REFER TO? NOT ALL PIPES
 ARE SIZED.
 16) SHT A1.05 TRANSFORMER VAULT, IS SUMP
 TO BE PIPED OR JUST FOR CONTAINMENT OF
 OILS IN CASE OF EMERGENCY?
 17) SHT A1.05 GARAGE EXHAUST AND AIR
 SUPPLY FLOOR DRAINS, TO STORM? WILL FIRE
 AND DOMESTIC PUMP RMS HAVE FLOOR DRAINS?
 18) SHT A1.05 FUEL TANK ROOM, CONTAIN-
 MENT IN CASE OF SPILLAGE?
 19) PLEASE SUBMIT CALCULATIONS FOR ALL
 PRIMARY AND SECONDARY ROOF DRAINS. ADD
 ALL AREAS OF ROOF THAT DRAIN FROM ABOVE
 AND 1/2 ALL AREA OF ALL VERTICAL WALLS.
 SHOW LOCATION OF ALL SECONDARY ROOF
 DRAINS. CALCULATE PER FBC PLMB SEC 1106
 & 1107, TABLES 1106.2, & 1106.3, FIGURE
 1106.1.
 20) PLEASE INDICATE MATERIALS USED FOR
 ALL PLUMBING SYSTEMS.
 21) PLEASE SHOW BACKFLOWS REQUIRED FOR
 MAKE UP WATER TO COOLING TOWERS, SWIMM-
 ING POOL, & IRRIGATION. PLEASE INDICATE
 MANUFACTURE AND MODEL NUMBER, AND LOCAT-
 ION OF EACH.
 22) SEPARATE PLANS AND PERMIT REQUIRED
 FOR POOL, & POOL EQUIPMENT ROOM. PLEASE
 ROUTE PLANS TO PALM BEACH HEALTH UNIT
 DIVISION OF ENVIRONMENTAL HEALTH 901
 EVERNIA STREET, WPB FL 33401 (561) 355-
 3018.
 23) PLEASE SUBMIT DETAILS FOR SAUNA AND
 STEAM ROOMS
 24) PLEASE SUBMIT WATER HEATER DETAILS.
 PROVIDE INFORMATION FOR SEC 504.7.1, THE
 DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP-
 ED SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS HEATER. SUBMIT INFO FOR
 THERMAL EXPANSION CONTROL, 607.3
 25) SHT A8.22 PLEASE SHOW CLEAR FLOOR
 SPACE FOR URNAL. (30"X48" MINIMUM)
 26) SHTS A8.33/A8.34 UNIT Q, FIREPLACE
 PLEASE SUBMIT DETAILS. SHOW EXHAUST DUCT
 IS THIS A GAS FIREPLACE?
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377