Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop M
Sequence Number 1
Notes
Date Text
2002-05-13 00:00:00 
 1.PLAN SHEET M1.06 - PLEASE CLARIFY
 DUCTS APPEAR TO BE IN ONE SHAFT.NOTE
 11 DRYER EXHAUST, NOTE 12 TRANSFER
 GRILLE AND THE 3RD IS NOT IDENTIFIED
 BUT APPEARS TO BE OUTSIDE AIR.AS PER
 2001 FBC(M) 603.8, CAVITIES IN FRAMED
 SPACES SHALL NOT BE USED TO DELIVER
 AIR FROM OR RETURN AIR TO CONDITIONING
 SYSTEM UNLESS THEY CONTAIN AN AIR DUCT
 INSERT INSULATED IN ACCORDANCE WITH
 TABLE 4-10 OR 6-10 CHAPTER 13 OF THE
 FBC.
  
 2.SHAFTS THAT CONSTITUTE AIR DUCTS OR
 ENCLOSE AIR DUCTS USED FOR ENVIRONMENTAL
 AIR SHALL NOT ENCLOSE: EXHAUST DUCTS
 USED FOR THE REMOVAL OF SMIKE & GREASE
 LADEN VAPORS FROM COOKING EQUIPMENT,
 DUCTS USED FOR CONVEYING VAPOR OR DUST,
 REFUSE & LINEN CHUTES, PIPING OR
 COMBUSTIBLE STORAGE.
  
 3.M1.07 CLARIFY DUCTWORK DOWN AT STAIR
 #2.NO FIRE DAMPERS ARE INDICATED.
 DUCTS SHALL NOT RUN IN THE STAIRWELL.
  
 4.M1.08 DUCTS TO THE CORRIDOR, FIRE
 DAMPERS ARE NOT INDICATED. 2001 FBC(M)
 607.6, SPECIFIC LOCATION & INSTALLATION
 DETAILS OF EACH FIRE DOOR, CEILING
 DAMPER AND FIRE & OR SMOKE DAMPERS
 SHALL BE SHOWN & PROPERLY IDENTIFIED ON
 PLANS.
  
 5.PLAN SHEET 4.11 DETAIL FOR GARAGE
 EXHAUST MUST HAVE A POSITIVE CONNECTION
 BETWEEN GRILLE & INTAKE TO FAN.
  
 6.OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3 & 307.2.4.
  
 7.PROVIDE DETAILS FOR THE GENERATOR
 EXHAUST.INDICATE TERMINATION IN
 COMPLIANCE WITH NFPA 110 5-10.
  
 8.PROVIDE STAIRWELL ELEVATION
 INDICATING LOCATION OF FAN, LOUVERS.
  
 9.INDICATE HOW DUCTWORK IS TO BE
 ACCESSED UNDER THE POOL AREA.WILL
 DUCTWORK HAVE ANY PROTECTION FROM
 MOISTURE, ELEMENTS OR DAMAGE?
  
 10. PROVIDE SEQUENCE OF OPERATION.
  
 11. PROVIDE TEST CRITERIA FOR SMOKE
 EVAC/CONTROL.
  
 12. OUTSIDE AIR CALCULATIONS SHALL
 PROVIDE COMPLIANCE WITH 402.2 (4% OF
 THE FLOOR AREA BDING VENTILATED) OR
 TABLE 403.3 (MECHANICAL VENTILATION NOT
 INFILTRATION).
  
 13. AS PER 2001 FBC(M) 602.2.1,
 MATERIALS EXPOSED WITHIN PLENUMS SHALL
 BE NONCOMBUSTIBLE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.