2002-05-13 00:00:00 | |
| 1.PLAN SHEET M1.06 - PLEASE CLARIFY |
| DUCTS APPEAR TO BE IN ONE SHAFT.NOTE |
| 11 DRYER EXHAUST, NOTE 12 TRANSFER |
| GRILLE AND THE 3RD IS NOT IDENTIFIED |
| BUT APPEARS TO BE OUTSIDE AIR.AS PER |
| 2001 FBC(M) 603.8, CAVITIES IN FRAMED |
| SPACES SHALL NOT BE USED TO DELIVER |
| AIR FROM OR RETURN AIR TO CONDITIONING |
| SYSTEM UNLESS THEY CONTAIN AN AIR DUCT |
| INSERT INSULATED IN ACCORDANCE WITH |
| TABLE 4-10 OR 6-10 CHAPTER 13 OF THE |
| FBC. |
| |
| 2.SHAFTS THAT CONSTITUTE AIR DUCTS OR |
| ENCLOSE AIR DUCTS USED FOR ENVIRONMENTAL |
| AIR SHALL NOT ENCLOSE: EXHAUST DUCTS |
| USED FOR THE REMOVAL OF SMIKE & GREASE |
| LADEN VAPORS FROM COOKING EQUIPMENT, |
| DUCTS USED FOR CONVEYING VAPOR OR DUST, |
| REFUSE & LINEN CHUTES, PIPING OR |
| COMBUSTIBLE STORAGE. |
| |
| 3.M1.07 CLARIFY DUCTWORK DOWN AT STAIR |
| #2.NO FIRE DAMPERS ARE INDICATED. |
| DUCTS SHALL NOT RUN IN THE STAIRWELL. |
| |
| 4.M1.08 DUCTS TO THE CORRIDOR, FIRE |
| DAMPERS ARE NOT INDICATED. 2001 FBC(M) |
| 607.6, SPECIFIC LOCATION & INSTALLATION |
| DETAILS OF EACH FIRE DOOR, CEILING |
| DAMPER AND FIRE & OR SMOKE DAMPERS |
| SHALL BE SHOWN & PROPERLY IDENTIFIED ON |
| PLANS. |
| |
| 5.PLAN SHEET 4.11 DETAIL FOR GARAGE |
| EXHAUST MUST HAVE A POSITIVE CONNECTION |
| BETWEEN GRILLE & INTAKE TO FAN. |
| |
| 6.OVERFLOW PROTECTION REQUIRED AS PER |
| 2001 FBC(M) 307.2.3 & 307.2.4. |
| |
| 7.PROVIDE DETAILS FOR THE GENERATOR |
| EXHAUST.INDICATE TERMINATION IN |
| COMPLIANCE WITH NFPA 110 5-10. |
| |
| 8.PROVIDE STAIRWELL ELEVATION |
| INDICATING LOCATION OF FAN, LOUVERS. |
| |
| 9.INDICATE HOW DUCTWORK IS TO BE |
| ACCESSED UNDER THE POOL AREA.WILL |
| DUCTWORK HAVE ANY PROTECTION FROM |
| MOISTURE, ELEMENTS OR DAMAGE? |
| |
| 10. PROVIDE SEQUENCE OF OPERATION. |
| |
| 11. PROVIDE TEST CRITERIA FOR SMOKE |
| EVAC/CONTROL. |
| |
| 12. OUTSIDE AIR CALCULATIONS SHALL |
| PROVIDE COMPLIANCE WITH 402.2 (4% OF |
| THE FLOOR AREA BDING VENTILATED) OR |
| TABLE 403.3 (MECHANICAL VENTILATION NOT |
| INFILTRATION). |
| |
| 13. AS PER 2001 FBC(M) 602.2.1, |
| MATERIALS EXPOSED WITHIN PLENUMS SHALL |
| BE NONCOMBUSTIBLE. |
| |
| |