2002-05-07 00:00:00 | 1) ADDRESS FOR BUILDING REQUIRED. A |
| MINIMUM OF SIX INCH NUMERALS REQUIRED. |
| |
| 2) TEMPORARY STANDPIPES ARE REQUIRED |
| WHEN THE BUILDING REACHES THREE STORIES |
| OR THIRTY FEET IN HEIGHT. |
| |
| 3) STAIRS ARE TO BE KEPT UP WITH |
| CONSTRUCTION. |
| |
| 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO, DURING AND AFTER CONSTRUCTION. |
| |
| 5) PLEASE BE ADVISED THAT THIS BUILDING |
| IS LOCATED WITHIN THE CITY FIRE LIMITS. |
| CERTAIN RESTRICTIONS APPLY. PLEASE |
| SEE CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FLORIDA BUILDING CODE. |
| |
| 6) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| THE WON ELEVATOR DOORS. |
| |
| 7) PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATION INFORMATION FOR WALLS |
| AND CEILINGS OF THE BUILDING. |
| |
| 8) CEDER TRELLISES NOTED ON LOWER ROOF |
| POOL DECK. AGAIN, THE BUILDING IS |
| LOCATED WITHIN THE CITY FIRE LIMITS |
| CERTAIN RESTRICTIONS APPLY. |
| |
| 9) EIFS NOTED ON BUILDING ELEVATIONS. |
| PLEASE SEE LOCAL AMENDMENTS REGARDING |
| ARCHITECTURAL TRIM IN THE FIRE LIMITS. |
| |
| 10) THE USE OF PROPANE BARBECUE GRILLS |
| ABOVE THE FIRST FLOOR ON THE BALCONIES |
| ARE PROHIBITED. |
| |
| 11) ALL SHAFTWAYS THAT ARE ACCESSIBLE |
| TO THE FIRE RESCUE DEPARTMENT WHICH |
| PERSONS CAN FALL INTO ARE TO BE MARKED |
| "SHAFTWAY IN RED LETTERS, SIX INCHES |
| HIGH ON A WHITE BACKGROUND" PER NFPA 1. |
| |
| 12) A KNOX-BOX WILL BE REQUIRED FOR |
| FIRE RESCUE ACCESS. |
| |
| 13) ALL STAIRS ARE TO BE PROVIDED WITH |
| SIGNAGE TO INDICATE THE STAIR, THE |
| STORY, THE TERMINUS TOP AND BOTTOM. |
| |
| 14) ALL CANVAS CANOPIES ARE TO BE FIRE |
| RETARDENT. |
| |
| 15) NO COMBUSTIBLE MATERIALS ARE ALLOWED |
| WITHIN THE RETURN AIR PLENUMS. |
| |
| 16) PLEASE INDICATE THAT ALL OF THE |
| PRESCRIPTIVE CODE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, SECTION 412.4.3 |
| "FIRE COMMAND STATIONS" ARE BEING MET. |
| |
| 17) SITE PLAN INDICATES A SIX INCH FIRE |
| LINE ENTERING THE BUILDING. ON ANOTHER |
| SHEET, IT DISPLAYS AN EIGHT INCH LINE. |
| PLEASE BE ADVISED THAT AN EIGHT INCH |
| LINE IS THE MINIMUM THAT WILL BE ALLOWED |
| FOR A 1000 GPM FIRE PUMP THAT HAS BEEN |
| PROPOSED. |
| |
| 18) SITE PLAN DOES NOT SHOW FIRE MAIN |
| SIZE ON OKEECHOBEE BOULEVARD. |
| |
| 19) THE FIRE LINE SHOWN RUNNING UNDER |
| THE BUILDING'S FOUNDATION IS NOT ALLOWED |
| BY THE CODE UNLESS NO OTHER ALTERNATIVE |
| IS AVAILABLE. |
| |
| 20) NO DETAILS PROVIDED FOR PRESSURE |
| RELIEF DEVICES PROPOSED. |
| |
| 21) PLEASE VERIFY THAT THE CENTRAL FIRE |
| SPRINKLER HEADS THAT ARE PLANNED FOR |
| USE ARE NOT ON THE VOLUNTARY RECALL |
| LIST, PLEASE SEE WWW. |
| SPRINKLERREPLACEMENT.COM. |
| |
| 22) FIRE SPRINKLER PLANS DO NOT NOTE |
| THAT PRESSURE TESTING IS REQUIRED FOR |
| ALL UNDERGROUND FIRE MAINS AND ABOVE |
| GROUND FIRE SPRINKLER PIPING. |
| |
| 23) AREAS OF THE FIRE SPRINKLER PLANS |
| ARE MISSING FIRE SPRINKLER PROTECTION. |
| |
| 24) PLEASE EXPLAIN EXITING RATIONALE |
| FROM THE PARKING GARAGE. |
| |
| 25) PLEASE INDICATE ON THE ELECTRICAL |
| PLANS THAT ALL SMOKE DETECTORS ARE TO |
| BE INSTALLED A MINIMUM OF THREE FEET |
| FROM AIR CONDITIONER DIFFUSERS. |
| |
| 26) PLEASE EXPLAIN PURPOSE OF |
| DIRECTIONAL EXIT SIGN NEAR OPEN STAIRWAY |
| ACCROSS FROM TOWNHOUSE SIX IN CORRDIOR. |
| |
| 27) MANUAL PULL STATION AND HORN STROBE |
| NOTED IN MIDDLE OF STAIRWAY ON PAGE |
| E1.08. |
| |
| 28) PLEASE EXPLAIN LEDGES. |
| |
| 29) IT WAS NOTED THAT SMOKE DETECTORS |
| ARE SHOWN IN THE CORRIDORS OF THE |
| BUILDING. PLEASE BE ADVISED THAT SPACING |
| OF THESE DETECTORS ARE NOT TO EXCEED |
| CODE REQUIREMENTS. PLEASE CHECK THE |
| SPACING OF THESE DEVICES. |
| |
| 30) NO ILLUMINATED EXIT SIGNS LOCATED |
| FOR THE SECOND LEVEL PARKING AREA. |
| |
| 31) FIRE ALARM NOTES SECTION NUMBER |
| TWELVE INDICATES THAT THE BUILDING WILL |
| BE CONSIDERED TWO SEPARATE BUILDINGS |
| ABOVE THE FIFTH FLOOR. PLEASE EXPLAIN |
| RATIONALE. |
| |
| 32) PLEASE INDICATE WHAT THE VOICE |
| EVACUATION PORTION OF THE FIRE ALARM |
| SYSTEM WILL INDICATE TO PERSONS WITHIN |
| THE BUILDING. |
| |
| 33) THE MECHANICAL PLANS MAKE REFERENCE |
| TO SECTION 412.5. HOW ARE THE OPERABLE |
| WINDOWS GOING TO BE IDENTIFIED. |
| |
| 34) PLEASE INDICATE THAT THE FUEL |
| SUPPLY TO OPERATE EMERGENCY POWER |
| IS AMPLE TO SUPPLY A MINIMUM OF TWO |
| HOURS PER FBC 412.7.1.2. |
| |
| 35) EMERGENCY LIGHTING REQUIRED FOR |
| FIRE PUMP ROOM. |
| |
| 36) THE PLANS SUBMITTED APPEAR TO BE |
| INCOMPLETE. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 659-8096,EXT.8497 |