Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-06 00:00:00*************** UNSAT *****************
  
 PLEASE NOTE THAT PLANS ARE NOT COMPLETE
 FOR SUFFICIENT REVIEW.
 PLEASE ALSO NOTE THAT SOME OF THE
 NOTES ARE SET AS TYPICAL FOR MANY UNITS.
  
  
 1)NOTE: PLEASE NOTE,E1.02 NOTE SAYS TO
 SEE E0.00 FOR ELEC RM DETAIL? PLEASE
 NOTE ELEC RM IS NOTE SHOWN ON THAT PAGE.
  
  
 2)NOTE: PLEASE NOTE THAT SOME NOTE ON
 E1.01,1.02 ETC MENTION TO SEE E1.05 FOR
 TYP UNITS AND THOSE UNITS ARE NOT SHOWN
 ON OTHER SHEET.? PLEASE NOTE THAT THIS
 IS TYP FOR OTHER SHEETS AS WELL.
  
 3)NOTE: PLEASE NOTE E1.05 ,SOME UNITS
 SHOWING TWO PANELS? (TH-1,TH-2 ETC )
 PLEASE CLARIFY. MISPRINT?
  
 4)NOTE: PLEASE NOTE THAT SOME UNIT IN
 THE BEGINING PART OF THE SETS ARE NOT
 SHOWING CATV. PLEASE NOTE IF CATV IS
 GOING TO BE THOSE UNITS, PLEASE REVISE
 AND SHOW.
  
 5)NOTE: PLEASE NOTE TYPICAL OF ALL UNITS
 PLEASE SHOW/CLARIFY GFI/GFI PROTECTION
 FOR ALL JACUZZI/SPA UNITS. 680-42
  
 6)NOTE: PLEASE NOTE MISSING HALLWAY REC
 210-52H. PLEASE NOTE MISSING INSOME UNIT
 -S.
  
 7)NOTE: PLEASE NOTE TYPICAL FOR MANY
 UNITS, 2` 6 ` RULE FOR RECEPT SPACING
 PER 210-52. PLEASE NOTE SOME UNITS ARE
 MISSING MORETHAN OTHERS.
  
 8)NOTE: PLEASE NOTE E1.20 PANEL SHOWN
 IN THE MIDDLE OF THE ROOM WITH OTHER
 EQUIPMENT?? PLEASE CLARIFY.
  
 9)NOTE: PLEASE NOTE THAT ALL SMOKE
 DETECTORS ARE TO BE A MIN OF 3' FROM
 BATHS RMS AND KITCHENS. NFPA-72 2-5.2.1.
 6.
  
 10)NOTE:PLEASE NOTE RECEPT SPACING FOR
 ALLKITCHENS COUNTERSPACES 210-52C-1
 PLEASE NOTE FOR 12", 24" ETC.
  
 11)NOTE: PLEASE NOTE PENINSULAR RECEPT
 SPACINGPER 210-52C-3. PLEASE NOTE THAT
 ANY INTERUPTION OF CONTINUOUS SPACE
 REQ`SADDTIONAL RECEPTS. (SINKS)
 * PLEASE NOTE MANY UNITS ARE MISSING
 RECEPTS PER 210-52C 1,2,3,4,5***
  
 12)NOTE: PLEASE NOTE E1.28 UNIT B2 SAYS
 SEE SIMULAR UNIT ON E1.29? PLEASE NOTE
 NOTHING SHOWN FOR THIS?
  
 13)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING PER 210-70. PLEASE NOTE MANY
 UNITS COMING INTO FOYER HAVE A FIXTURE/
 AND SOME DO NOT. PLEASE NOTE ANY OTHER
 LOCATIONS ON PLANS. SOME MISSING IN
 HALLWAYS AND /OR HABITABLE ROOMS.
  
 14)NOTE: PLEASE NOTE SOME PAGES/NOTES
 REFERENCE OTHER PAGES AND THAT INFORMAT-
 -ION IS NOT SHOWN. PLEASE GO OVER PLANS.
 E1.29ETC/
  
 15)NOTE: PLEASE NOTE OTHERS SHEETS/UNITS
 SHOWING TWO PANEL AND APPEAR TO BE
 A DOUBLE PRINT?
  
 16)NOTE:PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
 ROOF TOP.
  
 17)NOTE: PLEASE NOTE MISSING ELECTRICAL
 FOR ROOF TOP POOL/ POOL AREA /CABANAS??
  
 18)NOTE: PLEASE NOTE THAT SOME UNITS
 DO SHOW A/C UNIT CIRCUIT #`S ON PLANS
 BUT DO NOT CORRELATE WITH PANEL SCHEDULE
 (S). OTHER UNITS DO NOT SHOW ANY CIRCUIT
 #`S AT ALL. PLEASE SHOW .
 PLEASE NOTE SIZING OF OCP FOR AHU`S PER
 424-3B. PLEASE NOTE THAT KW RATINGS THAT
 ARE SHOWN DO NOT SEEM BE COMMON SIZE??
  
 19)NOTE: PLEASE NOTE METER CENTER(S) IS
 SHOWING TYP AS 600A AND SOME ARE SHOWN
 AS 800A? PLEASE CORRELATE AND CLARIFY.
  
 20)NOTE: PLEASE NOTE THAT THERE ARE SOME
 PANEL SCHEDULES SHOWNON SHEETS ARE NOT
 SHOWN ON RISER DIAGRAM.?? PLEASE SHOW.
  
 21)NOTE: PLEASE NOTE NO OCP / WIRE /
 CONDUIT SIZES SHOWN FOR FIRE PUMP.
 659-3,695-4,695-5
  
 22)NOTE: MISSING FEEDERS AND CONDUIT
 SIZES FOR MSB/ESB ,,,,,,
  
 23)NOTE: PLEASE NOTE NO GFI PROTECTION
 SHOWN FOR ANY OF THE 277V/480V SERVICES
 RATED FOR MORETHAN 1000AMPS.
 240-13/230-95
  
 24)NOTE: PLEASE NOTE ESB SHOWN AS 1600A
 ON RISER AND 1200A ON PNAEL SCHEDULE.
 PLEASE CORRELATE.
  
 25)NOTE: PLEASE NOTE MCN AND MCS ARE
 SHOWN AS 4000A AND MCS SHOWN AS 5000A
 ON SCHEDULE? PLEASE CORRELATE.
  
 26)NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 215-2,215-3,230-42
  
 27)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
 PLEASE NOTE THAT THERE IS NO GROUNDING
 DETAIL SHOWN.
  
 28)NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULES. PER 210-12
  
 29)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
 PLEASE NOTE THAT NO LOAD CALCULATIONS
 ARE SHOWN FOR HOUSE SERVICES. PLEASE
 SHOW.
  
 30) NOTE: PLEASE NOTE THAT ELECTRICAL
 SPEC BOOKS NEED TO BE SUBMITTED FOR
 REVIEW.
  
 31)NOTE: PLEASE NOTE PER LOCAL AMENDMENT
 -S. COLOR CODING OF FEEDERS NEED TO BE
 NOTED ON PLANS. PLEASE NOTE THAT THE
 LOCAL AMENDMENTS ARE SHOWN IN THE AMEND
 BOOKS THAT WERE HANDED OUT IN THE PRE-
 PLAN REVIEW MEETING.
  
 32)NOTE: PLEASE NOTE THAT ON E4.02,
 NOTE 19 SAYS "NOT USED", BUT IS # ON
 ELECTRICAL RISER DIAGRAM.??
  
 PLEASE COMPLETE PLANS AND SUBMIT ALL OF
 THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372