2002-05-07 00:00:00 | THE PLAN PACKAGE IS INCOMPLETE AND A |
| CLOSE AND CRITICAL PLAN REVIEW WAS NOT |
| POSSIBLE. |
| |
| SPECIFICATIONS, SOIL TEST REPORTS AND |
| WIND TUNNEL TESTING INFORMATION MUST BE |
| INCLUDED AT THE TIME OF PERMIT |
| APPLICATION. |
| |
| A RECENT PROPERTY SURVEY AND A |
| DIMENSIONED SITE PLAN WILL BE REQUIRED |
| AT TIME OF PERMIT APPLICATION. |
| |
| SEE FBC 104.3.1 SO THAT IT MAY ACT AS A |
| GUIDELINE AS TO THE INFORMATION TO BE |
| INCLUDED WITH THE PLANS TOGETHER WITH |
| THE CRITERIA SPECIFIED IN FBC 1606.1.7. |
| |
| THE PROPOSED BUILDING WILL BE TYPE I FS |
| CONSTRUCTION, GROUP R2 OCCUPANCY AND |
| SIXTEEN STORIES SINCE THE "ROOF |
| STRUCTURES" EXCEED 1/3 OF THE ROOR AREA |
| AS PROVIDE FOR IN FBC 1511.1.1.2. |
| |
| A THRESHOLD BUILDING INSPECTION PLAN AND |
| INSPECTOR WILL BE REQUIRED AS STATED |
| INFBC 105.13. |
| |
| BEFORE A PERMIT TO CONSTRUCT MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY, THE PERMIT PLANS |
| STAMPED BY THAT OFFICE, AND A COPY OF |
| THE PAID RECEIPT ATTCHED TO THE PERMIT |
| APPLICATION.CALL 561-233-5025 FOR |
| MORE INFORMATION. |
| |
| STAIR #1 DOES NOT PROVIDE A PROTECTED |
| EXIT TO THE EXTERIOR OF THE BUILDING |
| NOR DOES IT COMPLY WITH FBC 1010.1. |
| |
| SHEET LS1 DEPICTS THE WEST END OF THE |
| TWO CORRIDORS DISCHARGING INTO THE |
| GARAGE.THE PLANS ALSO INDICATE STEPS |
| THERE WHICH DO NOT COMPLY WITH FBC |
| 1003.2.7, A RAMP IS REQUIRED. |
| |
| SEE FBC 1003.2.7 FOR THE STEP |
| SPECIFICATIONS AT THE LOBBY DISCHARGE |
| ON THE EAST SIDE. |
| |
| THE LS PLANS DO NOT INDICATE THE |
| OCCUPANT LOADS SERVED OR THE EXIT |
| WIDTHS.SEE FBC 104.2. |
| |
| SHEET LS 2 AND OTHERS, DO NOT INDICATE |
| ANY EXITS ON THE WEST SIDE OF THE |
| GARAGE. |
| FBC 411.2.4 SPECIFICALLY PROHIBITS |
| TRAVEL ON THE PARKING RAMPS FOR EGRESS. |
| |
| STAIR SECTION 3 ON SHEET A7.04 SHOWS A |
| RISE OF MORE THAN TWELVE FEET FOR A |
| SINGLE FLIGHT OF STAIRS.SEE FBC |
| 1007.4.1. |
| |
| THE PLANS SHOW THE WALL ON THE WEST SIDE |
| AS A ZERO LOT LINE, FBC TABLE 600 |
| REQUIRES A FOUR HOUR FIRE RATING FOR |
| EXTERIOR BEARING WALLS.THE INTERIOR |
| BEARING WALLS ARE REQUIRED TO BE THREE |
| HOUR RATED.INCLUDE A FIRE DESIGN |
| NUMBER FOR THE MASONRY WALLS. |
| |
| A COMPLETE REVIEW FOR TABLE 600 IS NOT |
| POSSIBLE WITHOUT A SURVEY / SITE PLAN. |
| |
| THE USE OF EIFS TRIM IS NOT ALLOWED BY |
| FBC APPENDIX F 102.2.7 AS AMENDED BY |
| THE CITY AND FBC 1404.1 |
| |
| THE PLANS DO NOT SHOW A METHOD OR |
| SCHEDULE FOR THE PROTECTION OF FLOOR |
| AND WALL PENETRATIONS IN ACCORDANCE |
| WITH FBC 705.4. |
| |
| THE PLANS DO NOT CLEARLY DEPICT THE |
| PARAPETS OR GUARDRAIL SYSTEM TO BE USE |
| ON THE ROOF AREAS.SEE FBC 1015. |
| |
| SEE FBC 2810 FOR MARKING AND OTHER |
| REQUIERMENTS FOR INTAKE VENTS ON |
| LOCATED ON THE ROOF. |
| |
| SHOW SITE ACCESSIBILITY AS REQUIRE BY |
| FBC 11-4.1.2 (1). |
| |
| FBC 11-4.1.2 (5) (B) REQUIRES TWELVE |
| FEET WIDE PARKING SPACES FOR THE |
| HANDICAP. |
| |
| CITY AMENDMENTS TO FBC 2111.1.9 REQUIRE |
| A 1.5 INCH RECESS IN THE FLOOR SLABS FOR |
| EXTERIOR MASONRY WALLS. |
| |
| HOW WILL THE SMOKE VENTING OPENINGS |
| ALTERNATIVE CONTAINED IN FBC 412.5 (1) |
| BE ACCOMPLISHED IN THE WEST WALL |
| ELEVATIONS? |
| |
| THE FIRE PROTECTION PLANS ARE |
| INCOMPLETE, SEE SECTION 8-1.1.1 OF NFPA |
| 13-99 FOR INFORMATION TO BE PROVIDED ON |
| THE PLANS. |