Plan Review Notes
Plan Review Notes For Permit 02040459
Permit Number 02040459
Review Stop B
Sequence Number 1
Notes
Date Text
2002-05-07 00:00:00THE PLAN PACKAGE IS INCOMPLETE AND A
 CLOSE AND CRITICAL PLAN REVIEW WAS NOT
 POSSIBLE.
  
 SPECIFICATIONS, SOIL TEST REPORTS AND
 WIND TUNNEL TESTING INFORMATION MUST BE
 INCLUDED AT THE TIME OF PERMIT
 APPLICATION.
  
 A RECENT PROPERTY SURVEY AND A
 DIMENSIONED SITE PLAN WILL BE REQUIRED
 AT TIME OF PERMIT APPLICATION.
  
 SEE FBC 104.3.1 SO THAT IT MAY ACT AS A
 GUIDELINE AS TO THE INFORMATION TO BE
 INCLUDED WITH THE PLANS TOGETHER WITH
 THE CRITERIA SPECIFIED IN FBC 1606.1.7.
  
 THE PROPOSED BUILDING WILL BE TYPE I FS
 CONSTRUCTION, GROUP R2 OCCUPANCY AND
 SIXTEEN STORIES SINCE THE "ROOF
 STRUCTURES" EXCEED 1/3 OF THE ROOR AREA
 AS PROVIDE FOR IN FBC 1511.1.1.2.
  
 A THRESHOLD BUILDING INSPECTION PLAN AND
 INSPECTOR WILL BE REQUIRED AS STATED
 INFBC 105.13.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTCHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 STAIR #1 DOES NOT PROVIDE A PROTECTED
 EXIT TO THE EXTERIOR OF THE BUILDING
 NOR DOES IT COMPLY WITH FBC 1010.1.
  
 SHEET LS1 DEPICTS THE WEST END OF THE
 TWO CORRIDORS DISCHARGING INTO THE
 GARAGE.THE PLANS ALSO INDICATE STEPS
 THERE WHICH DO NOT COMPLY WITH FBC
 1003.2.7, A RAMP IS REQUIRED.
  
 SEE FBC 1003.2.7 FOR THE STEP
 SPECIFICATIONS AT THE LOBBY DISCHARGE
 ON THE EAST SIDE.
  
 THE LS PLANS DO NOT INDICATE THE
 OCCUPANT LOADS SERVED OR THE EXIT
 WIDTHS.SEE FBC 104.2.
  
 SHEET LS 2 AND OTHERS, DO NOT INDICATE
 ANY EXITS ON THE WEST SIDE OF THE
 GARAGE.
 FBC 411.2.4 SPECIFICALLY PROHIBITS
 TRAVEL ON THE PARKING RAMPS FOR EGRESS.
  
 STAIR SECTION 3 ON SHEET A7.04 SHOWS A
 RISE OF MORE THAN TWELVE FEET FOR A
 SINGLE FLIGHT OF STAIRS.SEE FBC
 1007.4.1.
  
 THE PLANS SHOW THE WALL ON THE WEST SIDE
 AS A ZERO LOT LINE, FBC TABLE 600
 REQUIRES A FOUR HOUR FIRE RATING FOR
 EXTERIOR BEARING WALLS.THE INTERIOR
 BEARING WALLS ARE REQUIRED TO BE THREE
 HOUR RATED.INCLUDE A FIRE DESIGN
 NUMBER FOR THE MASONRY WALLS.
  
 A COMPLETE REVIEW FOR TABLE 600 IS NOT
 POSSIBLE WITHOUT A SURVEY / SITE PLAN.
  
 THE USE OF EIFS TRIM IS NOT ALLOWED BY
 FBC APPENDIX F 102.2.7 AS AMENDED BY
 THE CITY AND FBC 1404.1
  
 THE PLANS DO NOT SHOW A METHOD OR
 SCHEDULE FOR THE PROTECTION OF FLOOR
 AND WALL PENETRATIONS IN ACCORDANCE
 WITH FBC 705.4.
  
 THE PLANS DO NOT CLEARLY DEPICT THE
 PARAPETS OR GUARDRAIL SYSTEM TO BE USE
 ON THE ROOF AREAS.SEE FBC 1015.
  
 SEE FBC 2810 FOR MARKING AND OTHER
 REQUIERMENTS FOR INTAKE VENTS ON
 LOCATED ON THE ROOF.
  
 SHOW SITE ACCESSIBILITY AS REQUIRE BY
 FBC 11-4.1.2 (1).
  
 FBC 11-4.1.2 (5) (B) REQUIRES TWELVE
 FEET WIDE PARKING SPACES FOR THE
 HANDICAP.
  
 CITY AMENDMENTS TO FBC 2111.1.9 REQUIRE
 A 1.5 INCH RECESS IN THE FLOOR SLABS FOR
 EXTERIOR MASONRY WALLS.
  
 HOW WILL THE SMOKE VENTING OPENINGS
 ALTERNATIVE CONTAINED IN FBC 412.5 (1)
 BE ACCOMPLISHED IN THE WEST WALL
 ELEVATIONS?
  
 THE FIRE PROTECTION PLANS ARE
 INCOMPLETE, SEE SECTION 8-1.1.1 OF NFPA
 13-99 FOR INFORMATION TO BE PROVIDED ON
 THE PLANS.