2002-04-19 00:00:00 | ************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT CODES FROM THE | | 96 NEC ARE STILL BEING REFERENCED ON | | PLANS. PLEASE NOTE THAT THESE ITEMS | | HAVE BEEN REDLINED FOR SOMETIME NOW AND | | NEED TO BE CORRECTED AND CORRELATE WITH | | THE 99 NEC. | | | | 2))NOTE: PLEASE CLARIFY EQUIPMENT | | GROUNDING METHOD BETWEEN FIRST MEANS | | OF DISCONNECT AND PANELS. PLEASE SIZE | | CONDUCTORS PER 250-122. | | | | 3 )NOTE: PLEASE LIST THE REQ`D ARC | | FAULT PROECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | PLEASE NOTE MISPRINT FOR AIC RATING, | | SHOWN AS 22.00 JUST A NOTE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICLA PLAN REVIEW | | 561-659-8096 EXT 8372 |
|