Plan Review Notes For Permit 02040429
Permit Number 02040429
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-19 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT CODES FROM THE
 96 NEC ARE STILL BEING REFERENCED ON
 PLANS. PLEASE NOTE THAT THESE ITEMS
 HAVE BEEN REDLINED FOR SOMETIME NOW AND
 NEED TO BE CORRECTED AND CORRELATE WITH
 THE 99 NEC.
  
 2))NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 3 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 PLEASE NOTE MISPRINT FOR AIC RATING,
 SHOWN AS 22.00 JUST A NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICLA PLAN REVIEW
 561-659-8096 EXT 8372