Plan Review Notes
Plan Review Notes For Permit 02040426
Permit Number 02040426
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-19 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT THE CODES
 REFERENCED ARE STILL FROM THE "96" NEC.
 PLEASE NOTE THE WE HAVE BEEN REDLINING
 THE 99 ARTS FOR SOMETIME. PLEASE MAKE
 CORRECTIONS TO CORRELATE WITH THE 99 NEC
  
 2)NOTE: PLEASE NOTE AIC RATING SHOWN AS
 22.00. PLEASE NOTE THIS MUST BE A
 MISPRINT.
  
 3))NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
  
 4))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372