Plan Review Notes For Permit 02040426 |
Permit Number |
02040426 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-19 00:00:00 | ************** UNSAT ***************** | | | | 1)NOTE: PLEASE NOTE THAT THE CODES | | REFERENCED ARE STILL FROM THE "96" NEC. | | PLEASE NOTE THE WE HAVE BEEN REDLINING | | THE 99 ARTS FOR SOMETIME. PLEASE MAKE | | CORRECTIONS TO CORRELATE WITH THE 99 NEC | | | | 2)NOTE: PLEASE NOTE AIC RATING SHOWN AS | | 22.00. PLEASE NOTE THIS MUST BE A | | MISPRINT. | | | | 3))NOTE: PLEASE CLARIFY EQUIPMENT | | GROUNDING METHOD BETWEEN FIRST MEANS | | OF DISCONNECT AND PANELS. PLEASE SIZE | | CONDUCTORS PER 250-122. | | | | | | 4))NOTE: PLEASE LIST THE REQ`D ARC | | FAULT PROECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|