2002-04-12 00:00:00 | DENIED |
| REFERENCE: FBC-2001 FUEL GAS |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-FUEL |
| GAS CODE. |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| 3. TYPE OF GAS, (LP OR NATURAL) |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 GAS CODE SECS. 402.1 THRU |
| 402.5.2 & TABLES 402(1) THRU 402(34). |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A. |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SEC 304.1 THRU 304..7 |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE APPENDIX A. |
| IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND FBC-2001 |
| FUEL GAS CODE SEC 301. |
| 9) SINCE A SIGNED AND SEALED RISER DIA- |
| GRAM WAS SUBMITTED ON A REVISION, THE |
| ISOMETRIC REFERENCED IN REVIEW COMMENT |
| #1 THIS REVIEW SHALL BE SIGNED AND SEAL- |
| ED BY ENGINEER OF RECORD. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |