Plan Review Notes
Plan Review Notes For Permit 02040386
Permit Number 02040386
Review Stop B
Sequence Number 1
Notes
Date Text
2002-05-13 00:00:00CHECKLIST:
 1-DESIGN CRITERIA:
 FBC 2001 SEC. 1606.2 SHALL NOT BE USED
 TO DESIGN A "PARTIALLY ENCLOSED" BLDG.
 SEE SEC. 1606.1.4.1 FBC 2001.
 2-TWO HR OVERHANG DETAIL FOR WD ASSEMBLY
 USING CALCULATED RATINGS IS NOT
 PERMITTED. SEE SEC. 709.6.1.2 FBC 2001
 3-UPDATE ALL PLANS AND SPECIFICATIONS.
 SEE COMMENTS ON PLANS AND RETURN
 REVIEWED SET TO EXPEDITE REVIEW.
 4-REVISE STRUCTURAL BUCK DETAILS TO
 SATISFY THE REQUIREMENTS OF SECTION
 1707.4.4 FBC 2001.
 5-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING INSTALLATION AT FRONT AND BACK
 PORCHES. SEE ASTM C-1063 FOR SPECIFIC
 FASTENERS AND SPACING. & ASTM C-926.
 SECTION 2504.2 FBC 2001.
 6-CLARIFY FASTENING OF GARAGE DOOR BUCK.
 SEE DRAWING 1 ON DS-1 AND DET. 4 ON S4
 7-REVISE ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA. SEE SECTION
 604.1.A.1 OF CHAPTER 13 OF FBC 2001.
 B)THIS IS MULTIFAMILY BLDG NOT SINGLE
 FAMILY. SEE DEFINITIONS ON CHAPTER
 13 OF FBC 2001.SPECIFY # OF UNITS.
 8-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE REPORT SUBMITTED WAS DELETED
 FROM SBCCI. NEED UPDATED ONE.
 9-CONCRETE SLAB NOTES: ADD SPECIFICATION
 FOR SUPPORTS AS REQUIRED BY SECTION
 1909.3 FBC 2001.
 10-UPDATE ALL CONNECTORS SPECIFIED
 THROUGHOUT DRAWINGS. "HUGHES" AND
 "SEMCO" ARE OUT OF BUSINESS.
 11-CLARIFY SPECIFICATIONS FOR SOIL
 BEARING CAPACITY IS IT 2000PSF OR
 2500PSF. SEE SHEET S-11 AND TITLE
 SHEET. REVISE AS REQUIRED.
  
  
 NOTES:
 -THESE COMMENTS APPLY TO PERMIT #S
 02040386, 02040391, 02040393 & 02040395
 -DRAWINGS AND PERMITS TO BE FILED UNDER
 PERMIT #02040386.