Plan Review Notes For Permit 02040368 |
Permit Number |
02040368 |
|
Review Stop |
P |
Sequence Number |
8 |
|
Notes |
Date |
Text |
2003-12-13 00:00:00 | DENIED; | | 1.PLANS ARE NOT SIGNED SEE FL. ADMINIS- | | TRATIVE CODE SEC. 61G15-23.002 ( COPY | | ENCLOSED ). | | 2.PLANS SHOW WASHER DRYER ON FIRST AND | | SECOND FLOOR.RISER DIAGRAM SHOWS W/M ON | | FIRST FLOOR. PLEASE CORRECT. | | 3.RISER DIAGRAM; | | A.FIRST FLOOR BATHROOM CANNOT DIS- | | CHARGE INTO THE SECOND FLOOR | | BATHROOM SANITARY RISER. | | B.WASHING MACHINE VENT MUST RE-VENT | | 6" ABOVE THE HIGHEST FIXTURE ON | | THE SECOND FLOOR. | | C.TOTAL FIXTURE UNITS IS 14 NOT 18. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|