Date |
Text |
2003-08-14 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | CODE REQUIREMENTS. | | A) 909.1 ONLY THE FIXTURES WITHIN THE | | BATHROOM GROUPS SHALL CONNECT TO THE WET | | VENTED HORIZONTAL BRANCH DRAIN. ANY | | ADDITIONAL FIXTURES SHALL DISCHARGE | | DOWNSTREAM OF THE WET VENT. WASHMACHINES | | B) BATHTUB P-TRAPS CANNOT BE TAKEN OFF | | ABOVE THE WASHMACHINE AND THE WATER | | CLOSET AND THE CLEANOUT.????? WATER | | CLOSET AND TUB SHOULD BE CONNECTED ON | | THE HORIZONTAL BELOW THE FLOOR WITH THE | | CLEANOUT AND LAV ABOVE THE FLOOR | | C) SANITARY RISER DIAGRAM SHOWS A KIT. | | SINK ON THE SECOND FLOOR, BUT THE FLOOR | | PLAN DOES NOT SHOW A KITCHEN SINK. | | 3) SEE ATTACHED SHEET FOR EXAMPLE OF | | APPROVED BATHROOM/WASH MACHINE RISER | | DIAGRAM. - SUBMIT A RISER DIAGRAM THAT | | MEETS CODE AND REFLECTS FLOOR PLAN. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|