Date Text
2003-08-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS.
 A) 909.1 ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. WASHMACHINES
 B) BATHTUB P-TRAPS CANNOT BE TAKEN OFF
 ABOVE THE WASHMACHINE AND THE WATER
 CLOSET AND THE CLEANOUT.????? WATER
 CLOSET AND TUB SHOULD BE CONNECTED ON
 THE HORIZONTAL BELOW THE FLOOR WITH THE
 CLEANOUT AND LAV ABOVE THE FLOOR
 C) SANITARY RISER DIAGRAM SHOWS A KIT.
 SINK ON THE SECOND FLOOR, BUT THE FLOOR
 PLAN DOES NOT SHOW A KITCHEN SINK.
 3) SEE ATTACHED SHEET FOR EXAMPLE OF
 APPROVED BATHROOM/WASH MACHINE RISER
 DIAGRAM. - SUBMIT A RISER DIAGRAM THAT
 MEETS CODE AND REFLECTS FLOOR PLAN.
  
 REVIEW BY KEN STEVENS