Notes
Date Text
2003-12-15 00:00:00DENIED
  
 1) THE WINDOW AND DOOR PRESSURES ON A2
 ARE INCORRECT. THE MAXIMUM PRESSURES
 FOR THE STRUCTURE ARE THE SAME FOR BOTH
 FLOORS AND ARE BASED ON A TWO STORY
 STRUCTURE. PLEASE CORRECT.
  
 2) THE NEGATIVE PRESSURE SPECIFIED ON
 THE PLANS OF -57 PSF EXCEEDS THE
 NEGATIVE DESIGN PRESSURES OF THE DOORS
 AND THE 35 SINGLE HUNG WINDOWS. SEE THE
 PRODUCT APPROVALS. PLEASE CORRECT.
 NOTE: REVIEW THE SPECIFIED WIND LOAD
 PRESSURES. THE FBC TABLE 1606.2B FOR A
 STRUCTURE WITH A MEAN ROOF HEIGHT OF 30'
 OR LESS WITH EXPOSURE B LISTS THE
 MAXIMUM PRESSURES AS +35.3 AND -47.2 PSF
  
 3) THE ID MARKS ON THE DOOR SCHEDULE DO
 NOT CORRESPOND TO THE ID MARKS ON THE
 PLANS.
  
 4) CHANGE THE WINDOW SIZES ON SHEETS A3
 AND P1 TO CORRESPOND WITH A2.
  
 5) THE PRODUCT APPROVALS FOR THE JELD-
 WEN DOOR, THE SHINGLES AND STORM PANELS
 HAVE EXPIRED. SUBMIT CURRENT PRODUCT
 APPROVALS.
  
 6) THE INSTALLATION SCHEDULE FOR THE
 STORM PANELS HAS ERRORS. PLEASE CORRECT.
 THE GLAZING IN THE DOORS ARE REQUIRED TO
 BE SHUTTERED. SPECIFY THE ANCHOR TYPE
 AND REQUIRED SPACING OF THE ANCHORS AS
 INDICATED ON THE PRODUCT APPROVAL.
  
 7) THE ORIGINAL WET SIGNATURE AND DATE
 AS WELL AS THE EMBOSSD SEAL OF THE
 ENGINEER ARE REQUIRED ON EACH PAGE OF
 PLANS AND ON ALL DRAWINGS FROM HIM.
  
 8) PLEASE REVIEW THE EAST & WEST
 ELEVATIONS FOR COMPLIANCE WITH FBC
 TABLE 600 REQUIREMENTS. THE AREA OF WALL
 ALLOWED AS OPENINGS IS 20% ON THE EAST
 SIDE AND 40% ON THE WEST SIDE. THE
 LARGER EGRESS WINDOWS MAY EXCEED THE
 ALLOWABLE AREA. SUBMIT YOUR CALCULATIONS
 FOR THESE TWO ELEVATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714