2003-04-04 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| |
| PLAN REVIEW COMMENTS FROM 5-8-2, 10-5-2 |
| 12/5/2 & 2-28-3 HAVE NOT BEEN ADDRESSED. |
| |
| 1) SHT A2, 1 AAUTOMATIC CLOTHES WASHER |
| CONNECTION REQUIRED FOR EACH UNIT OR A |
| CENTRAL FACILITY WITH 1 CONNECTION PER |
| 20 UNITS REQUIRED PER TABLE 403.1. |
| 2) SHT P1 PLUMBING NOTES #'2 2, 5, 6, 7, |
| 8, 9, 10, & 11. CURRENT CODE IS FBC-2001 |
| PLUMBING, NOT SFBC AS STATED IN NOTES. |
| PLEASE CHANGE NOTES TO REFLECT PRESENT |
| PLUMBING CODE. |
| 3) SHT P2 1ST & 2ND FLOOR WATER RISER |
| DIAGRAMS, AIR CHAMBERS ARE NOT APPROVED. |
| WATER HAMMER ARRESTORS SHALL BE PROVIDED |
| PER SECTION 604.9 AND LOCATED PER PDI-WH |
| 201 AND MANUF. INSTALLATION INSTRUCTIONS |
| 4) SHT P2 SANITARY RISER DIAGRAM, 2ND |
| FLOOR BATHROOM GROUP SHALL NOT DRAIN IN- |
| TO VENT OF 1ST FLOOR BATHROOM GROUP. 2ND |
| FLOOR STACK SHALL BE TAKEN OFF BLDG |
| DRAIN DOWNSTREAM OF 1ST FLOOR BATHROOM |
| GROUP. |
| 5) SHT P2 SANITARY RISER DIAGRAM, 3" |
| VENT REQUIRED FOR MAIN STACK PER SEC. |
| 903.1 |
| 6) SEE ATTACHED SHEET CONCERNING FLORIDA |
| STATUTE 553.80(2) (B). ADDITIONAL FEES |
| SHALL BE IMPOSED AS THIS IS THE FIFTH |
| TIME THESE COMMENTS HAVE BEEN ADDRESSED. |
| |
| |