Plan Review Notes
Plan Review Notes For Permit 02040368
Permit Number 02040368
Review Stop B
Sequence Number 5
Notes
Date Text
2003-10-20 00:00:00BUILDING DENIED
  
 1) ENERGY CALCULATIONS ARE REQUIRED TO
 BE SIGNED AND DATED BY THE OWNER/AGENT.
 FBC CHAPTER 13.
  
 2) SPECIFY THE ROOF PITCH, MEAN ROOF
 HEIGHT, HEIGHT OF FLOORS AND CEILINGS
 ABOVE GRADE ON THE ELEVATIONS.
  
 3) THE PRODUCT APPROVALS SUBMITTED ARE
 FOR JELD-WEN "GLAZED" EXTERIOR STEEL
 DOORS.THE SCHEDULE ON THE PLANS SPECIFY
 STANLEY DOORS W/ ACCEPTANCE #00-0512.09.
 THE SCHEDULE SPECIFIES ALUMNIUM DOORS.
 PLEASE REVISE.
  
 4) THE 34 SH WINDOWS SPECIFIED ON THE
 PLANS DO NOT PROVIDE THE CLEAR OPENING
 SIZE REQUIRED FOR EMERGENCY ESCAPE AND
 RESCUE OPENINGS BY FBC 1005.4.4.
  
 5) THE PLANS SPECIFY BINNINGS PAN
 AMERICAN WINDOWS WITH ACCEPTANCE #
 01-0226.04. THE PRODUCT APPROVALS THAT
 WERE SUBMITTED ARE FOR TRACO WINDOWS.
  
 6) THE SIZES SPECIFIED IN THE SCHEDULE
 FOR THE 14SH, 1/2 33SH AND 1/2 34SH
 WINDOWS ARE INCORRECT. PLEASE CORRECT.
  
 7) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE CONNECTOR TYPE & SPACING AND TYPE OF
 MOUNT THAT WILL BE USED.
  
 8) THE WALL SECTIONS ON A-5 DO NOT
 SPECIFY A CONCRETE CAP WITH HORIZONTAL
 REINFORCEMENT OR VERTICAL REINFORCEMENT
 AND FILLED CELLS TYING THE STEM WALL TO
 THE FOOTER. A CONTINOUS LOAD PATH FROM
 THE ROOF TO THE FOOTING IS REQUIRED.
 SPECIFY ON THE PLAN HOW THE LOAD WILL BE
 TRANSFERED FROM THE TOP OF THE STEM WALL
 TO THE FOUNDATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714