2003-08-14 00:00:00 | DENIED |
| |
| 1)SUBMIT ENERGY CALCULATIONS AS REQUIRED |
| BY FBC CHAPTER 13. |
| |
| 2) PROVIDE TWO COPIES OF A KEY PLAN AND |
| INSTALLATION SCHEDULE FOR THE STORM |
| PANELS. NOTE: THE PRODUCT APPROVALS THAT |
| WERE SUBMITTED FOR THE STORM PANELS ARE |
| EXPIRED. PLEASE SUBMIT CURRENT ONES. |
| |
| 3) SUBMIT A SIGNED AND SEALED SURVEY |
| INDICATING THE LOCATION OF THE STRUCTURE |
| ON THE PROPERTY AND THE DISTANCE TO THE |
| PROPERTY LINES. THIS IS REQUIRED TO |
| DETERMINE THE PERCENT OF WALL AREA THAT |
| IS ALLOWED AS OPENINGS. FBC TABLE 600 |
| |
| 4) PROVIDE EXTERIOR ELEVATIONS. INDICATE |
| THE HEIGHT ABOVE GRADE TO FLOORS, |
| CEILINGS, ETC. INDICATE THE MEAN ROOF |
| HEIGHT AND PITCH. |
| |
| 5)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - THE EXTERIOR ALUMINUM DOORS |
| PRODUCT APPROVALS THAT WERE SUBMITTED |
| ARE FOR STEEL DOORS. IF YOU ARE USING |
| STEEL EXTERIOR DOORS, PLEASE REVISE THE |
| DOOR SCHEDULE ON THE PLANS. |
| |
| 6) THE ITEMS THAT ARE REDLINED ON THE |
| PLANS ARE REQUIRED TO BE INITALED AND |
| DATED BY THE DESIGNER OF RECORD. |
| |
| 7) THE DOOR/WINDOW PRESSURES LISTED ON |
| A-2 CONFLICT WITH THOSE ON A-1. PLEASE |
| CORRECT. |
| |
| 8) THE WINDOW SCHEDULE ON A-2 DOES NOT |
| INCLUDE THE 34 SH WINDOWS SPECIFIED ON |
| THE FLOOR PLAN. THE WRONG SIZES ARE |
| GIVEN FOR THE 14SH, 1/2 33SH AND |
| 1/2 34SH WINDOWS. PLEASE CORRECT. |
| |
| 9) SPECIFY THE SPACING OF THE THE MTS 30 |
| CONNECTORS ON A-5. |
| |
| 10) THE WALL SECTIONS ON A-5 DO NOT |
| INDICATE A CAP BEAM ON TOP OF THE STEM |
| WALL WITH DOWN BARS CONNECTING TO THE |
| FOOTER. A CONTINOUS TIE FROM THE ROOF TO |
| THE FOOTING IS REQUIRED TO TRANSFER THE |
| LOADS TO THE GROUND. SPECIFY HOW THIS |
| WILL BE ACHIEVED. |
| |
| 11) SEVERAL OF THESE COMMENTS WERE NOTED |
| IN PREVIOUS REVIEWS AND HAVE NOT BEEN |
| ADDRESSED. SEE FL STATUTE 553.80 (2) (B) |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |