Date |
Text |
2002-12-03 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| |
| 1) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| SHT A2, 1 AUTOMATIC CLOTHES WASHER CON- |
| NECTION REQUIRED FOR EACH UNIT OR A CEN- |
| TRAL FACILITY WITH 1 CONNECTION PER 20 |
| UNITS REQUIRED PER TABLE 403.1 |
| 2) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| SHT P1 PLUMBING NOTES, #'S 2, 5, 6, 7, 8 |
| 9, 10, & 11. CURRENT CODE IS FBC-2001 |
| PLUMBING, NOT SFBC AS STATED IN NOTES. |
| PLEASE CHANGE NOTES TO REFLECT PRESENT |
| PLUMBING CODE. |
| 3) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| SHT P1 PLUMBING NOTES #2 SHEET Z1 REFER- |
| ENCED IN NOTE NOT SUBMITTED. PLEASE SUB- |
| MIT ALL SHEETS FOR REVIEW. |
| 4) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| SHT P2 1ST & 2ND FLOOR WATER WATER RISER |
| DIAGRAMS, AIR CHAMBERS ARE NOT APPROVED. |
| WATER HAMMER ARRESTORS SHALL BE PROVIDED |
| FOR WASH MACHINE, ICE MAKER, AND DISH |
| WASHER IF PROVIDED. SEC 604.9 |
| 5) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| SHT P2 SANITARY RISER DIAGRAM, 2ND FLOOR |
| BATHROOM GROUP SHALL NOT DRAIN INTO VENT |
| OF 1ST FLOOR BATHROOM GROUP VENT. 2ND |
| FLOOR STACK SHALL BE TAKEN OFF BLDG |
| DRAIN DOWNSTREAM OF 1ST FLOOR BATHROOM |
| GROUP. FLOOR PLAN DOES NOT SHOW KITCHEN |
| ON SECOND FLOOR |
| 6) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2 |
| SHT P2 SANITARY RISER DIAGRAM, 3" VENT |
| REQUIRED FOR MAIN STACK VENT PER SECTION |
| 903.1 |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |