Plan Review Notes
Plan Review Notes For Permit 02040368
Permit Number 02040368
Review Stop P
Sequence Number 3
Notes
Date Text
2002-12-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2
 SHT A2, 1 AUTOMATIC CLOTHES WASHER CON-
 NECTION REQUIRED FOR EACH UNIT OR A CEN-
 TRAL FACILITY WITH 1 CONNECTION PER 20
 UNITS REQUIRED PER TABLE 403.1
 2) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2
 SHT P1 PLUMBING NOTES, #'S 2, 5, 6, 7, 8
 9, 10, & 11. CURRENT CODE IS FBC-2001
 PLUMBING, NOT SFBC AS STATED IN NOTES.
 PLEASE CHANGE NOTES TO REFLECT PRESENT
 PLUMBING CODE.
 3) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2
 SHT P1 PLUMBING NOTES #2 SHEET Z1 REFER-
 ENCED IN NOTE NOT SUBMITTED. PLEASE SUB-
 MIT ALL SHEETS FOR REVIEW.
 4) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2
 SHT P2 1ST & 2ND FLOOR WATER WATER RISER
 DIAGRAMS, AIR CHAMBERS ARE NOT APPROVED.
 WATER HAMMER ARRESTORS SHALL BE PROVIDED
 FOR WASH MACHINE, ICE MAKER, AND DISH
 WASHER IF PROVIDED. SEC 604.9
 5) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2
 SHT P2 SANITARY RISER DIAGRAM, 2ND FLOOR
 BATHROOM GROUP SHALL NOT DRAIN INTO VENT
 OF 1ST FLOOR BATHROOM GROUP VENT. 2ND
 FLOOR STACK SHALL BE TAKEN OFF BLDG
 DRAIN DOWNSTREAM OF 1ST FLOOR BATHROOM
 GROUP. FLOOR PLAN DOES NOT SHOW KITCHEN
 ON SECOND FLOOR
 6) FROM PREVIOUS REVIEWS 5-8-2 & 10-5-2
 SHT P2 SANITARY RISER DIAGRAM, 3" VENT
 REQUIRED FOR MAIN STACK VENT PER SECTION
 903.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377