2003-04-14 00:00:00 | BUILDING DENIED |
| |
| 1) FBC 1606.1.7 WIND LOADS. THE PLANS |
| SHALL STATE THE BASIC WIND SPEED, WIND |
| IMPORTANCE FACTOR, WIND EXPOSURE |
| CATEGORY, INTERNAL PRESSURE COEFFICENT, |
| AND EXTERIOR COMPONENT AND CLADDING |
| DESIGN WIND PRESSURES. THIS INFORMATION |
| IS REQUIRED TO BE ON THE PLANS. |
| |
| 2) SHEETS A2 AND A4 CONTAIN REFERENCES |
| TO THE WRONG CODE AND INCORRECT DESIGN |
| CRITERIA. PLEASE CORRECT. |
| |
| 3) PROVIDE ENERGY CALCULATIONS. SEE FBC |
| CHAPTER 13. |
| |
| 4) THE FASTENER SCHEDULE ON A4 REFERS TO |
| SOUTH FLORIDA BUILDING CODE UNDER THE |
| REMARKS COLUMN. PLEASE CORRECT TO FBC. |
| |
| 5)CORRECT NOTE #11 UNDER TYPICAL SECTION |
| NOTES ON A4 AND THE DRYWALL FASTENER |
| SPACING SPECIFIED ON DETAIL 1 AND DETAIL |
| 5 ON A5 TO COMPLY WITH FBC TABLE 2306.1. |
| |
| 6) SPECIFY ON THE PLANS THAT ADEQUATE |
| SUBSTRATE WILL BE PROVIDED AT THE |
| WINDOWS FOR ATTACHMENT OF THE STORM |
| PANELS. |
| |
| 7) PROVIDE (2) COPIES OF INSTALLATION |
| SCHEDULE AND KEY PLAN FOR STORM PANELS. |
| NOTE: THE PRODUCT APPROVALS THAT WERE |
| SUBMITTED FOR STORM PANELS HAS EXPIRED. |
| PLEASE SUBMIT CURRENT ONES. |
| |
| 8) STUCCO ON METAL LATH OVER SOLID BASE |
| IS REQUIRED BY FBC 2504.2.1 AND ASTM C |
| 926 TO BE 7/8" THICK. PLEASE REVISE ON |
| WALL SECTIONS. |
| |
| 9) INDICATE THE ATTIC ACCESS ON THE |
| PLANS. SEE FBC 2309.6. |
| |
| 10) FBC 1005.4 REQUIRES SLEEPING ROOMS |
| TO HAVE AN EMERGENCY ESCAPE AND RESCUE |
| OPENING. SEE CLEAR OPENING SIZE AND AREA |
| REQUIREMENTS. THE 1/2- 34SH WINDOWS |
| SHOWN ON THE PLANS DO NOT COMPLY. |
| |
| 11) PROVIDE DETAILS OF THE INTERIOR AND |
| EXTERIOR STAIRS. SPECIFY THE RISER |
| HEIGHTS AND TREAD DEPTHS. INDICATE THE |
| FOUNDATION THAT SUPPORTS THE EXTERIOR |
| STAIRS. |
| |
| 12) PROVIDE A SIGNED AND SEALED SURVEY |
| INDICATING THE LOCATION OF THE STRUCTURE |
| ON THE PROPERTY AND THE DISTANCE TO THE |
| PROPERTY LINES. THIS IS REQUIRED TO |
| DETERMINE THE PERCENT OF WALL AREA THAT |
| IS ALLOWED AS OPENINGS. |
| |
| 13)PROVIDE EXTERIOR ELEVATIONS. INDICATE |
| THE HEIGHT ABOVE GRADE TO FLOORS, |
| CEILINGS, ETC. INDICATE THE MEAN ROOF |
| HEIGHT AND ROOF PITCH. |
| |
| 14) SPECIFY THE POSITIVE AND NEGATIVE |
| DESIGN WINDLOAD PRESSURES ON THE PLANS |
| FOR ALL EXTERIOR OPENINGS. |
| |
| 15) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - EXTERIOR WOOD DOOR |
| - EXTERIOR ALUMINUM DOOR |
| THESE ARE THE EXTERIOR DOORS THAT ARE |
| SPECIFIED ON THE PLANS IN THE DOOR |
| SCHEDULE ON ON A2. IF YOU ARE NOT USING |
| THESE DOORS, CHANGE THE SCHEDULE TO |
| INDICATE THE DOORS THAT WILL BE USED. |
| |
| 16) THE DOOR SCHEDULE INDICATES THAT TWO |
| EXTERIOR DOORS ARE HOLLOW CORE WOOD. |
| THIS IS NOT ALLOWED BY FBC CHAPTER 13. |
| (ENERGY EFFICIENCY) |
| |
| 17) THE COMMENTS NOTED IN PREVIOUS |
| REVIEWS HAVE NOT BEEN ADDRESSED. FL |
| STATUTE 553.80 (2) (B) REQUIRES A FEE OF |
| FOUR TIMES THE PLAN REVIEW PORTION OF |
| THE PERMIT FEE TO BE IMPOSED FOR EACH |
| TIME AFTER THE THIRD REVIEW IN WHICH THE |
| SAME ITEM HAS NOT BEEN CORRECTED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |