Plan Review Notes
Plan Review Notes For Permit 02040368
Permit Number 02040368
Review Stop P
Sequence Number 2
Notes
Date Text
2002-10-05 00:00:00DENIED;
 PLAN REVIEW COMMENTS FROM 5/8/02 HAVE
 NOT BEEN ADDRESSED.NOTES FROM 5/8/02 ARE
 LISTED BELOW.
  
 1.SHT AE. 1 AUTOMATIC CLOTHES WASHER
 CONNECTION REQUIRED FOR EACH UNIT OR A
 CENTRAL FACILITY WITH 1 CONNECTION PER
 20 UNITS REQUIRED PER TABLE 403.1.
 2.3/4 " PAN DRAIN LINE REQUIRED FOR ALL
 PANS INSTALLED. PAN DRAIN TO TERMINATE
 OUTSIDE 6" ABOVE GRADE.
 3.NOTES ON SHEET P-1 CURRENT CODE IS
 FBC-2001 NOT SFBC. PLEASE CHANGE NOTES
 TO REFLECT PRESENT PLUMBING CODE.
 4.SHT P-1 PLUMBING NOTE 1 SHT Z-1
 REFERENCED IN NOTE WAS NOT SUBMITED
 WITH PLANS.
 5.AIR CHAMBERS ARE NOT APPROVED. WATER
 HAMER ARRESTORS SHALL BE INSTALLED PER
 FBC 2001.
 6.SHT P-2 SANITARY RISER DIAGRAM. SECOND
 FLOOR BATHROOM GROUP SHALL NOT DRAIN
 INTO THE VENT FOR THE FIRST FLOOR.
 RISER DIAGRAM SHOWS A KITCHENSINK ON
 SECOND FLOOR, FLOOR PLAN DOESNOT SHOW
 KITCHEN.
 7.SHT P-2 SANITARY RISER DIAGRAM 3" VENT
 REQUIRED FOR MAIN STACK VENT PER SEC.
 903.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369