Plan Review Notes For Permit 02040368 |
Permit Number |
02040368 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-10-05 00:00:00 | DENIED; | | PLAN REVIEW COMMENTS FROM 5/8/02 HAVE | | NOT BEEN ADDRESSED.NOTES FROM 5/8/02 ARE | | LISTED BELOW. | | | | 1.SHT AE. 1 AUTOMATIC CLOTHES WASHER | | CONNECTION REQUIRED FOR EACH UNIT OR A | | CENTRAL FACILITY WITH 1 CONNECTION PER | | 20 UNITS REQUIRED PER TABLE 403.1. | | 2.3/4 " PAN DRAIN LINE REQUIRED FOR ALL | | PANS INSTALLED. PAN DRAIN TO TERMINATE | | OUTSIDE 6" ABOVE GRADE. | | 3.NOTES ON SHEET P-1 CURRENT CODE IS | | FBC-2001 NOT SFBC. PLEASE CHANGE NOTES | | TO REFLECT PRESENT PLUMBING CODE. | | 4.SHT P-1 PLUMBING NOTE 1 SHT Z-1 | | REFERENCED IN NOTE WAS NOT SUBMITED | | WITH PLANS. | | 5.AIR CHAMBERS ARE NOT APPROVED. WATER | | HAMER ARRESTORS SHALL BE INSTALLED PER | | FBC 2001. | | 6.SHT P-2 SANITARY RISER DIAGRAM. SECOND | | FLOOR BATHROOM GROUP SHALL NOT DRAIN | | INTO THE VENT FOR THE FIRST FLOOR. | | RISER DIAGRAM SHOWS A KITCHENSINK ON | | SECOND FLOOR, FLOOR PLAN DOESNOT SHOW | | KITCHEN. | | 7.SHT P-2 SANITARY RISER DIAGRAM 3" VENT | | REQUIRED FOR MAIN STACK VENT PER SEC. | | 903.1 | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT 8369 |
|