2003-02-20 00:00:00 | BUILDING DENIED |
| THIS IS THE FOURTH STRUCTURAL REVIEW. |
| |
| 1) THE ENTIRE STRUCTURE SHALL BE MADE TO |
| CONFORM THE REQUIREMENTS FOR A NEW |
| STRUCTURE PER FBC 3401.7.2.6 AND THE |
| CONSTRUCTION BOARD OF ADJUSTMENT AND |
| APPEALS. |
| |
| 2) A SUCCESSOR PROFESSIONAL ENGINEER |
| MUST USE HIS OWN TITLE BLOCK, SEAL AND |
| SIGNATURE AND MUST REMOVE THE TITLE |
| BLOCK, SEAL AND SIGNATURE OF THE |
| ORIGINAL PROFESSIONAL ENGINEER BEFORE |
| REUSING ANY SEALED CONTRACT DOCUMENTS. |
| SEE FAC 61G15-27 FOR REQUIREMENTS. |
| |
| 3) FBC 1606.1.7WIND LOAD.THE PLANS |
| SHALL STATE THE BASIC WIND SPEED, WIND |
| IMPORTANCE FACTOR, WIND EXPOSURE |
| CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| AND EXTERIOR COMPONENT AND CLADDING |
| DESIGN WIND PRESSURES. |
| |
| 4) SHEETS A2 AND A4 REFERENCE THE WRONG |
| CODE AND DESIGN CRITERIA. PLEASE |
| CORRECT. |
| |
| 5) PROVIDE ENERGY CALCULATIONS. SEE FBC |
| CHAPTER 13. |
| |
| 6) THE FASTENER SCHEDULE ON A4 CONTAINS |
| INCORRECT INFORMATION. REFER TO FBC |
| TABLE 2306.1 AND CORRECT. |
| |
| 7) PLEASE CORRECT NOTE 11 ON A4 AND DRY- |
| WALL FASTENER SPACING NOTE ON A5 TO |
| COMPLY WITH FBC TABLE 2306.1. |
| |
| 8) SPECIFY ON THE PLANS ADEQUATE |
| SUBSTRATE AT WINDOWS FOR THE ATTACHMENT |
| OF STORM PANELS. |
| |
| 9) PROVIDE KEY PLANS AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. |
| |
| 10) STUCCO ON METAL LATH IS REQUIRED TO |
| BE 7/8" THICK PER FBC 2504.2.1 AND ASTM |
| C 926. PLEASE REVISE ON WALL SECTIONS. |
| |
| 11) INDICATE THE ATTIC ACCESS ON THE |
| PLANS. SEE FBC 2309.6 |
| |
| 12) FBC 1005.4 REQUIRES SLEEPING ROOMS |
| TO HAVE AN EMERGENCY ESCAPE AND RESCUE |
| OPENING. SEE CLEAR OPENING SIZE AND AREA |
| REQUIREMENTS. |
| |
| 13) PROVIDE DETAILS OF INTERIOR AND |
| EXTERIOR STAIRS. SPECIFY THE RISER |
| HEIGHT AND TREAD DEPTH. INDICATE THE |
| FOUNDATION THAT SUPPORTS EXTERIOR STAIRS |
| |
| 14) PROVIDE A SIGNED AND SEALED SURVEY |
| INDICATING THE LOCATION OF THE STRUCTURE |
| ON THE PROPERTY AND THE DISTANCE TO THE |
| PROPERTY LINES, IN ORDER TO DETERMINE |
| COMPLIANCE WITH FBC TABLE 600. |
| |
| 15) PROVIDE EXTERIOR ELEVATIONS. |
| INDICATE HEIGHTS ABOVE GRADE TO FLOORS, |
| CEILINGS, ETC. INDICATE MEAN ROOF HEIGHT |
| AND ROOF PITCH. |
| |
| 16) SPECIFY THE POSITIVE AND NEGATIVE |
| DESIGN WINDLOAD PRESSURES ON THE PLANS |
| FOR ALL EXTERIOR OPENINGS. |
| |
| 17) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - EXTERIOR WOOD DOOR |
| - EXTERIOR ALUMNIUM DOOR |
| THESE DOORS ARE SPECIFIED IN THE DOOR |
| SCHEDULE ON A2. |
| |
| 18) THE DOOR SCHEDULE INDICATES THAT |
| TWO EXTERIOR DOORS ARE HOLLOW CORE WOOD. |
| THIS IS NOT ALLOWED BY FBC CHAPTER 13. |
| (FL ENERGY CODE) |
| |
| 19) THE STRUCTURE IS REQUIRED TO BE |
| RETURNED TO A SINGLE FAMILY DWELLING BY |
| THE ZONING DEPARTMENT. PLEASE REVISE THE |
| DRAWINGS TO REFLECT THIS. REMOVE THE |
| SECOND FLOOR KITCHEN AND CHANGE TITLE |
| BLOCK. |
| |
| MOST OF THESE COMMENTS WERE MADE IN THE |
| THREE PREVIOUS REVIEWS AND HAVE NOT BEEN |
| ADDRESSED. THE SAME PLANS HAVE BEEN |
| SUBMITTED WITH NO REVISIONS BEING MADE. |
| FLORIDA STATUTE 553.80(2)(B) REQUIRES A |
| FEE OF FOUR TIMES THE PLAN REVIEW |
| PORTION OF THE PERMIT FEE TO BE IMPOSED. |
| SEE ATTACHMENT. |
| IF YOU HAVE ANY QUESTIONS CALL: |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |