2002-09-30 00:00:00 | DENIED BY BUILDING |
| |
| 1) STRUCTURE MUST REMAIN A SINGLE FAMILY |
| RESIDENCE PER CITY OF WPB ZONING |
| DEPARTMENT. THEREFORE, ITEMS 1 AND 13 ON |
| FIRST REVIEW ARE NOT REQUIRED. PLEASE |
| REVISE SHEET 1 FROM MULTIFAMILY TO |
| SINGLE FAMILY. |
| |
| 2) THE ENTIRE STRUCTURE IS REQUIRED TO |
| BE MADE TO CONFORM TO THE REQUIREMENTS |
| FOR A NEW STRUCTURE DUE TO THE REPAIRS |
| AMOUNTING TO MORE THAN 50% OF THE VALUE |
| OF THE EXISTING BUILDING. SEE 2001 FBC |
| SECTION 3401.7.2.6. |
| |
| 3) PROVIDE ENERGY CALCULATIONS AND |
| MANUAL J CALCULATIONS AS REQUIRED BY THE |
| FBC CHAPTER 13. |
| |
| 4) INDICATE DESIGN INFORMATION ON PLANS. |
| 2001 FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 5) SHEETS A2 AND A4 REFERENCE THE WRONG |
| CODE AND DESIGN CRITERIA. PLEASE REVISE. |
| THE 2001 FLORIDA BUILDING CODE AND |
| ASCE 7-98 ARE THE PROPER REFERENCES. |
| |
| 6) PLEASE REVISE THE CODE REFERENCES ON |
| A4 TO FLORIDA BUILDING CODE IN THE |
| FASTENER SCHEDULE. REVISE #12 UNDER |
| TYPICAL SECTION NOTES TO REFERENCE |
| ASCE 7-98. |
| |
| 7) REVISE ITEM #9 UNDER TYPICAL SECTION |
| NOTES ON A4 TO ALL WINDOWS. |
| |
| 8) INDICATE ON THE PLANS THAT ADEQUATE |
| SUBSTRATE IS TO BE PROVIDE FOR THE |
| ATTACHMENT OF THE STORM PANELS. |
| |
| 9) PROVIDE (2) COPIES OF AN INSTALLATION |
| SCHEDULE AND KEY PLAN FOR THE HURRICANE |
| PANELS. |
| |
| 10) PLEASE REVISE SHEET A3 WHICH SHOWS A |
| KITCHEN ON THE SECOND FLOOR. |
| |
| 11) INDICATE THE UNDER FLOOR INSULATION |
| AT THE FIRST FLOOR AS REQUIRED BY FBC |
| CHAPTER 13. |
| |
| 12) STUCCO ON LATHE AS INDICATED ON WALL |
| SECTIONS ON A5 IS REQUIRED TO BE 7/8" |
| THICK PER FBC 2504.2.1 AND ASTM C 926. |
| |
| 13) A CONTINOUS LOAD PATH FROM THE ROOF |
| TO THE FOUNDATION IS REQUIRED TO |
| TRANSFER THE LOADS. NO CONNECTORS ARE |
| SHOWN ON A5 TO CONNECT THE BOTTOM PLATE |
| AND FLOOR JOISTS TO SILL PLATE AT THE |
| FIRST FLOOR. NO CONNECTORS ARE INDICATED |
| FROM TOP PLATES ON FIRST FLOOR TO BOTTOM |
| PLATE OF SECOND FLOOR. INDICATE THESE |
| CONNECTORS ON THE PLANS. |
| |
| 14) FIREBLOCKING IS REQUIRED BETWEEN THE |
| FLOOR AND WALL ASSEMBLIES ON THE FIRST |
| AND SECOND FLOORS PER FBC 2305.1. PLEASE |
| SHOW THIS ON THE PLANS. INDICATE THE |
| LOCATION AND MATERIALS USED TO DRAFTSTOP |
| THE FLOOR/CEILING ASSEMBLY INTO 500 SQFT |
| AREAS PER FBC 2305.2.2. |
| |
| 5) INDICATE THE ATTIC ACCESS ON THE |
| PLANS THAT COMPLIES WITH 2309.6. |
| |
| 16) EMERGENCY ESCAPE AND RESCUE OPENINGS |
| ARE REQUIRED AT SLEEPING ROOMS PER 2001 |
| FBC 1005.4. THE 1/2 34SH WINDOWS DO NOT |
| PROVIDE REQUIRED NET CLEAR OPENING AREA |
| FOR THE SECOND FLOOR OR THE CLEAR |
| OPENING HEIGHT. THE ROOMS WHICH HAVE |
| CLOSETS MUST ALSO COMPLY. |
| |
| 17) INTERIOR AND EXTERIOR STAIRS MUST BE |
| MADE TO COMPLY WITH 2001 FBC. PROVIDE |
| DETAILS OF STAIRS, HANDRAILS AND GUARD- |
| RAILS. THE INTERMEDIATE RAILS ON THE |
| STAIRS MUST REJECT THE PASSAGE OF A 4" |
| DIAMETER SPHERE THROUGH ANY OPENING. THE |
| PICKETS INDICATED ON SHEET A2 DO NOT |
| COMPLY. |
| |
| 18) PROVIDE COPIES OF SURVEY INDICATING |
| DISTANCES TO THE PROPERTY LINES IN ORDER |
| TO DETERMINE COMPLIANCE WITH TABLE 600 |
| FOR PERCENT OF WALL AREA ALLOWED AS WALL |
| OPENINGS. |
| |
| 19) PROVIDE ELEVATIONS. INDICATE FLOOR, |
| CEILING, CRAWL SPACE, ETC. ELEVATIONS. |
| INDICATE THE MEAN ROOF HEIGHT AND ROOF |
| PITCH ON THE PLANS. |
| |
| 20) INDICATE THE POSITIVE AND NEGATIVE |
| WINDLOAD PRESSURES FOR ALL EXTERIOR DOOR |
| AND WINDOW OPENINGS ON THE PLANS. |
| |
| 21) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - EXTERIOR WOOD DOOR |
| - EXTERIOR ALUMINUM DOOR |
| THE PRODUCT APPROVAL THAT WAS SUBMITTED |
| IS FOR AN EXTERIOR STEEL DOOR WHICH IS |
| NOT INDICATED ON THE PLANS. |
| |
| 22) THE DOOR SCHEDULE ON A2 INDICATES |
| HOLLOW CORE WOOD EXTERIOR DOORS. CHAPTER |
| 13 OF THE FBC DOES NOT ALLOW THIS TYPE |
| OF DOOR TO BE USED AT THE EXTERIOR. |
| PLEASE REVISE. |
| |