Date |
Text |
2002-05-08 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING. |
| |
| 1) SHT A2, 1 AUTOMATIC CLOTHES WASHER |
| CONNECTION REQUIRED FOR EACH UNIT OR A |
| CENTRAL FACILITY WITH I CONNECTION PER |
| 20 UNITS REQUIRED PER TABLE 403.1 |
| 2) SHT P1, WATER HEATER DETAIL, SHUT OFF |
| VALVE REQUIRED FOR WATER HEATER. EMERGEN |
| CY DRAIN PAN REQUIRED FOR ALL HEATERS |
| ABOVE FIRST FLOOR. 3/4" PAN DRAIN LINE |
| REQUIRED FOR PAN TERMINATING 6" ABOVE |
| GRADE. |
| 3) SHT P1 PLUMBING NOTES, #'S 2,5,6,7,8, |
| 9,10, & 11. CURRENT CODE IS FBC-2001 |
| PLUMBING, NOT SFBC AS STATED IN NOTES. |
| PLEASE CHANGE NOTES TO REFLECT PRESENT |
| PLUMBING CODE. |
| 4) SHT P1 PLUMBING NOTES, NOTE #2 SHEET |
| Z1 REFERENCED IN NOTE NOT SUBMITTED. |
| PLEASE SUBMIT ALL SHEETS FOR REVIEW. |
| 5) SHT P2 1ST & 2ND FLOOR WATER RISER |
| DIAGRAMS, AIR CHAMBERS ARE NOT APPROVED. |
| WATER HAMMER ARRESTORS SHALL BE PROVIDED |
| FOR WASH MACHINE, ICE MAKER, & DISHWASH- |
| ER IF PROVIDED. LOCATE W.H.A. NEAR FIX- |
| TURE IN AN "EFFECTIVE RANGE" NOT AT TOP |
| OF DROP. |
| 6) SHT P2 SANITARY RISER DIAGRAM, 2ND |
| FLOOR BATHROOM GROUP SHALL NOT DRAIN IN- |
| TO VENT OF 1ST FLOOR BATHROOM GROUP VENT |
| 2ND FLOOR STACK SHALL BE TAKEN OFF BLDG |
| DRAIN DOWNSTREAM OF 1ST FLOOR BATHROOM |
| GROUP. |
| 7) SHT P2 SANITARY RISER DIAGRAM, 3" |
| VENT REQUIRED FOR MAIN STACK VENT PER |
| SEC 903.1 |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |