Plan Review Notes
Plan Review Notes For Permit 02040368
Permit Number 02040368
Review Stop B
Sequence Number 1
Notes
Date Text
2002-05-13 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
 DUE TO THE CHANGE FROM A SINGLE FAMILY
 DWELLING TO A DUPLEX ADDITION IMPACT
 FEES MAY BE DUE TO PALM BEACH COUNTY.
  
 2) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY CHAPTER 13 OF THE FLORIDA
 BUILDING CODE, THE FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 3) INDICATE DESIGN INFORMATION ON PLANS.
 2001 FLORIDA BUILDING CODE AND ASCE7-98
 NOT SFBC OR ASCE7-93. SHEETS A2 AND A4
 REFERENCE THE WRONG CODE AND DESIGN
 CRITERIA.
  
 4) FASTENING SCHEDULE ON A4 CONTAINS
 INCORRECT INFORMATION. PLEASE REFER TO
 TABLE 2306.1 IN THE 2001 FBC AND MAKE
 CORRECTIONS.
  
 5) PLEASE CORRECT NOTE 11 ON A4 AND
 DRYWALL FASTENER SPACING NOTE ON A5 TO
 COMPLY WITH 2001FBC TABLE 2306.1 OR AS
 SPECIFIED BY MANUFACTURER.
  
 6) INDICATE ON THE PLANS THAT ADEQUATE
 SUBSTRATE IS TO BE PROVIDED FOR THE
 ATTACHMENT OF STORM PANELS.
  
 7) PROVIDE (2) COPIES OF AN INSTALLATION
 SCHEDULE AND KEY PLAN FOR HURRICANE
 PANELS.
  
 8) STUCCO ON LATHE AS INDICATED ON WALL
 SECTIONS ON A5 IS REQUIRED TO BE 7/8"
 THICK PER FBC 2504.2.1 AND ASTM C 926.
  
 9) A CONTINOUS LOAD PATH FROM THE ROOF
 TO THE FOUNDATION IS REQUIRED TO
 TRANSFER LOADS. NO CONNECTORS ARE SHOWN
 ON A5 BETWEEN THE FLOOR SILL AND STUDS
 OR BETWEEN 1ST AND 2ND FLOORS. PLEASE
 CORRECT.
  
 10) FIREBLOCKING IS REQUIRED BETWEEN THE
 FLOOR AND WALL ASSEMBLIES AT THE 1ST AND
 2ND FLOORS PER FBC 2305.1. PLEASE
 INDICATE ON PLANS.
  
 11) INDICATE ATTIC ACCESS ON PLANS.
 FBC 2309.6
  
 12) EMERGENCY ESCAPE AND RESCUE OPENINGS
 ARE REQUIRED AT SLEEPING ROOMS PER FBC
 1005.4. THE 1/2- 34SH WINDOWS INDICATED
 DO NOT PROVIDE THE REQUIRED NET CLEAR
 OPENING. PLEASE CORRECT.
  
 13) A ONE HOUR TENANT SEPARATION IS
 REQUIRED BETWEEN UNITS PER FBC 704.2.2.3
 AND 704.3.1.
  
 14) INDICATE HOW THE REQUIRED MEANS OF
 EGRESS FROM THE SECOND FLOOR UNIT WILL
 BE PROVIDED. EXIT STAIRWAYS SHALL COMPLY
 WITH FBC 1006. PROVIDE STAIR DETAILS.
  
 15) PROVIDE COPIES OF SURVEY INDICATING
 DISTANCES TO PROPERTY LINES IN ORDER TO
 DETERMINE COMPLIANCE WITH TABLE 600 FOR
 PERCENT OF WALL OPENINGS ALLOWED.
  
 16) PROVIDE ELEVATIONS. INDICATE FLOOR,
 CEILING,ETC. HEIGHTS. INDICATE MEAN ROOF
 HEIGHT AND ROOF PITCH.
  
 17) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR ALL EXTERIOR DOOR AND
 WINDOW OPENINGS ON THE PLANS.
  
 18) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR WOOD DOOR
 - EXTERIOR ALUMINUM DOOR
 THE PRODUCT APPROVAL THAT WAS SUBMITTED
 WAS FOR EXTERIOR STEEL DOOR, WHICH IS
 NOT LISTED IN THE DOOR SCHEDULE ON A2.
  
 19) THE DOOR SCHEDULE INDICATES THE
 EXTERIOR WOOD DOOR WITH A HOLLOW CORE.
 THIS IS NOT ALLOWED BY THE FLORIDA
 ENERGY CODE (FBC CHAPTER 13).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202