2002-05-13 00:00:00 | BUILDING DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| DUE TO THE CHANGE FROM A SINGLE FAMILY |
| DWELLING TO A DUPLEX ADDITION IMPACT |
| FEES MAY BE DUE TO PALM BEACH COUNTY. |
| |
| 2) PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY CHAPTER 13 OF THE FLORIDA |
| BUILDING CODE, THE FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILDING |
| CONSTRUCTION. |
| |
| 3) INDICATE DESIGN INFORMATION ON PLANS. |
| 2001 FLORIDA BUILDING CODE AND ASCE7-98 |
| NOT SFBC OR ASCE7-93. SHEETS A2 AND A4 |
| REFERENCE THE WRONG CODE AND DESIGN |
| CRITERIA. |
| |
| 4) FASTENING SCHEDULE ON A4 CONTAINS |
| INCORRECT INFORMATION. PLEASE REFER TO |
| TABLE 2306.1 IN THE 2001 FBC AND MAKE |
| CORRECTIONS. |
| |
| 5) PLEASE CORRECT NOTE 11 ON A4 AND |
| DRYWALL FASTENER SPACING NOTE ON A5 TO |
| COMPLY WITH 2001FBC TABLE 2306.1 OR AS |
| SPECIFIED BY MANUFACTURER. |
| |
| 6) INDICATE ON THE PLANS THAT ADEQUATE |
| SUBSTRATE IS TO BE PROVIDED FOR THE |
| ATTACHMENT OF STORM PANELS. |
| |
| 7) PROVIDE (2) COPIES OF AN INSTALLATION |
| SCHEDULE AND KEY PLAN FOR HURRICANE |
| PANELS. |
| |
| 8) STUCCO ON LATHE AS INDICATED ON WALL |
| SECTIONS ON A5 IS REQUIRED TO BE 7/8" |
| THICK PER FBC 2504.2.1 AND ASTM C 926. |
| |
| 9) A CONTINOUS LOAD PATH FROM THE ROOF |
| TO THE FOUNDATION IS REQUIRED TO |
| TRANSFER LOADS. NO CONNECTORS ARE SHOWN |
| ON A5 BETWEEN THE FLOOR SILL AND STUDS |
| OR BETWEEN 1ST AND 2ND FLOORS. PLEASE |
| CORRECT. |
| |
| 10) FIREBLOCKING IS REQUIRED BETWEEN THE |
| FLOOR AND WALL ASSEMBLIES AT THE 1ST AND |
| 2ND FLOORS PER FBC 2305.1. PLEASE |
| INDICATE ON PLANS. |
| |
| 11) INDICATE ATTIC ACCESS ON PLANS. |
| FBC 2309.6 |
| |
| 12) EMERGENCY ESCAPE AND RESCUE OPENINGS |
| ARE REQUIRED AT SLEEPING ROOMS PER FBC |
| 1005.4. THE 1/2- 34SH WINDOWS INDICATED |
| DO NOT PROVIDE THE REQUIRED NET CLEAR |
| OPENING. PLEASE CORRECT. |
| |
| 13) A ONE HOUR TENANT SEPARATION IS |
| REQUIRED BETWEEN UNITS PER FBC 704.2.2.3 |
| AND 704.3.1. |
| |
| 14) INDICATE HOW THE REQUIRED MEANS OF |
| EGRESS FROM THE SECOND FLOOR UNIT WILL |
| BE PROVIDED. EXIT STAIRWAYS SHALL COMPLY |
| WITH FBC 1006. PROVIDE STAIR DETAILS. |
| |
| 15) PROVIDE COPIES OF SURVEY INDICATING |
| DISTANCES TO PROPERTY LINES IN ORDER TO |
| DETERMINE COMPLIANCE WITH TABLE 600 FOR |
| PERCENT OF WALL OPENINGS ALLOWED. |
| |
| 16) PROVIDE ELEVATIONS. INDICATE FLOOR, |
| CEILING,ETC. HEIGHTS. INDICATE MEAN ROOF |
| HEIGHT AND ROOF PITCH. |
| |
| 17) INDICATE THE POSITIVE AND NEGATIVE |
| PRESSURES FOR ALL EXTERIOR DOOR AND |
| WINDOW OPENINGS ON THE PLANS. |
| |
| 18) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - EXTERIOR WOOD DOOR |
| - EXTERIOR ALUMINUM DOOR |
| THE PRODUCT APPROVAL THAT WAS SUBMITTED |
| WAS FOR EXTERIOR STEEL DOOR, WHICH IS |
| NOT LISTED IN THE DOOR SCHEDULE ON A2. |
| |
| 19) THE DOOR SCHEDULE INDICATES THE |
| EXTERIOR WOOD DOOR WITH A HOLLOW CORE. |
| THIS IS NOT ALLOWED BY THE FLORIDA |
| ENERGY CODE (FBC CHAPTER 13). |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |