2002-04-26 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE CODE ARTS ARE STILL
 BEING REF FROM 96 NEC. PLEASE CORRELATE
 W/ 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR AIC
 RATING. SHOWN AS 22.00? SHOULD BE
 22,000.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4)NOTE: PLEASE NOTE MISSING ARC FAULT
 PROTECTION PER 210-12 PLEASE SHOW AS
 NOTE OR LIST ON PANEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW